background image

LP-436 Rev. 5.20.15

13

Power Venter (Part #)

Vent Termination (Part #)

Kit #1

6060-200

6060-202

Kit #2

6060-201

6060-203

Table 5 - Power Venter and Vent Termination Part Numbers

Water Heater 

Model

Kit 

#

Draft 

Hood 

Outlet

Vent 

Size

Vent 

Adapter

Vent 

Reducer 

Location

CG125N73

1

5”

4”

5”-4”

1

CG150N73

2

6”

6”

Not Req.

-

CG199N73(X)

2

CG250N65

2

7”

7”-6”

1

CG300N65

2

8”

8”-6”

Table 6 - Vent Sizing, by Model Number

Figure 12 - Power Venter and Vent Termination

NOTE:

 Vent pipe is not included with the water heater.

When the installation is complete, visually inspect the venting 
system  to  make  sure  that  all  joints  are  properly  connected 
and  all  instructions  have  been  followed.  Failure  to  properly 
install  the  venting  system  can  result  in  property  damage, 
personal injury, or death.

E. Water Piping

Refer to Figure 13 for a typical installation. Use of this layout 
should  provide  a  trouble-free  installation  for  the  life  of  the 
water heater. Before making the plumbing connections, locate 
the COLD water inlet and the HOT water outlet. These fittings 
are both 1 ½” NPT male thread. Install a shut-off valve close to 
the water heater in the cold water line. It is recommended that 
unions be installed in the cold and hot water lines so that the 
water heater can be easily disconnected if service is required.

NOTE:

  It  is  recommended  to  use  dielectric  unions  when 

connecting to the water heater.
When assembling the hot and cold piping, use food grade pipe 
joint compound and ensure all fittings are tight. It is imperative 
that open flame is not applied to the inlet and outlet fittings, 
as heat will damage or destroy the plastic lined fittings. This 
will  result  in  premature  failure  of  the  fittings,  which  is  not 

covered by warranty.

1. Temperature and Pressure Relief Valve

DO NOT plug the temperature and pressure relief valve or its 
discharge line. DO NOT remove the relief valve. Make sure the 
relief valve is  properly  sized  for  the  water heater.  If  the  relief 
valve  continuously  discharges  water,  call  a  qualified  service 
technician  to  correct  the  problem.  Failure  to  follow  these 
instructions can result in property damage, personal injury, or 
death.

To  protect  from  excessive  pressure  and/or  temperature,  the 
manufacturer  has  installed  a  temperature  and  pressure  relief 
valve  that  meets  the  requirements  of  the  Standard  for  Relief 
Valves  and  Automatic  Gas  Shut-Off  Devices  for  Hot  Water 
Supply Systems, ANSI Z21.22 in the United States, and CSA 4.4 
in Canada. This relief valve has a maximum set pressure that does 
not exceed the hydrostatic working pressure of the water heater 
(150 psi = 1,035 kPa) and a BTU/H rating equal to or greater than 
the input rating, as shown on the water heater rating plate. It 
should never be plugged or removed from the opening marked 
for it on the water heater.
If this relief valve should need to be replaced, use only a new 
temperature  and  pressure  relief  valve.  Never  install  an  old  or 
existing  relief  valve,  as  it  may  be  damaged  or  inadequate  for 
the  working  requirements  of  the  new  water  heater. This  new 
relief  valve  must  meet  all  local  codes,  or,  at  minimum,  the 
requirements listed above. Never install any other type of valve 
between the relief valve and the water heater.
A  discharge  line  must  be  installed  into  the  relief  valve.  The 
discharge line:

•  Must not be smaller than the outlet pipe size of the relief 

valve.

•  Must not terminate less than 6” (15.2 cm) and not more 

than 12” (30.5 cm) above a floor drain.

•  Must not be restricted in any way. Do not thread, cap, or 

in any way restrict the end of this outlet.

•  Must  be  of  a  material  capable  of  withstanding  210

o

(99

o

C) without distortion.

•  Must be installed to allow complete drainage of the relief 

valve and discharge line.

•  Must terminate at an adequate free-flowing drain.

2. Pressure Build-Up in a Water System

When  the  water  heater  operates,  the  heated  water  expands 
creating a pressure build-up. This is a natural function and is one 
of the reasons for installing a temperature and pressure relief 
valve. If the cold water supply line has a built-in water meter, 
check  valve,  or  pressure-reducing  valve,  a  suitable  expansion 
tank  must  be  installed  to  prevent  pressure  build-up  or  water 
hammer  effect.  Otherwise,  the  warranty  is  void.  See  Figure 
13.  An  indication  of  pressure  build-up  is  frequent  relief  valve 
discharge. If the relief valve discharges water on a continuous 
basis,  it  may  indicate  a  malfunction  of  the  relief  valve  and  a 
qualified service technician must be called to have the system 
checked and the problem corrected.

Содержание CG N65 Series

Страница 1: ...l injury or death HTPreservestherighttomakeproductchangesorupdateswithoutnoticeandwillnotbeheldliablefortypographical errors in literature NOTETO CONSUMER PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFER...

Страница 2: ...CINITY OFTHIS OR ANY OTHER APPLIANCE WHATTO DO IFYOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch Do not use any phone in your building Immediately call your gas supp...

Страница 3: ...dividual such as a fire chief fire marshal chief of a fire prevention bureau labor department or health department building official or For the Installer This water heater must be installed by qualifi...

Страница 4: ...RSONAL INJURY OR DEATH DO NOT USE THIS WATER HEATER IF ANY PART HAS BEEN SUBMERGED IN WATER Immediately call a qualified service technician The water heater MUST BE replaced if it has been submerged A...

Страница 5: ...require a 120oF or lower temperature setting to prevent severe personal injury or death due to scalding F Water Temperature Adjustment If the water heater is going to have a set temperature above 120...

Страница 6: ...DS concentration will greatly accelerate lime and scale formation in the hot water system Most high TDS concentrations precipitate out of the water when heated This can generate a scale accumulation t...

Страница 7: ...water heater See Figure 13 for proper installation The drain pan should be at least 4 10 2 cm larger than the diameter of the water heater and at least 1 2 5 cm deep providing access to the drain val...

Страница 8: ...dern buildings additional fresh air may need to be provided For instructions on obtaining additional air supply see the requirements for confined spaces 2 Requirements for Confined Spaces In the US re...

Страница 9: ...for all the appliances installed in that confined space See Figure 7 When ducts are used they shall be of the same cross sectional area as the free area of the openings to which they connect The mini...

Страница 10: ...afthood assembly is installed Failure to follow these instructions can result in property damage personal injury or death When installing the water heater make sure the location allows clear viewing o...

Страница 11: ...stallation with a TjernlundTM side wall power vent kit See Figure 10 This kit can be installed as part of a new installation or retrofitted onto an existing installation The kit consists of a power ve...

Страница 12: ...tally L Clearance above paved sidewalk or paved driveway located on public property 7 2 13 m M Clearance under veranda porch deck or balcony 12 Table 3 Side Wall PowerVentTermination Requirements 1In...

Страница 13: ...ssure and or temperature the manufacturer has installed a temperature and pressure relief valve that meets the requirements of the Standard for Relief Valves and Automatic Gas Shut Off Devices for Hot...

Страница 14: ...ates or CAN CSA B149 1 NationalGas and Propane InstallationCode in Canada Only new piping with cleanly cut threads may be used The water heater and its gas connection must be leak tested before placin...

Страница 15: ...ly manual shut off valve must be closed NOTE Theinputratingoftheapplianceisbasedoninstallation and operation at sea level up to elevations of 2 000 ft Low NOx models are certified to operate to 2 000...

Страница 16: ...o disconnecting Verify all wiring connections before relighting the water heater Wiring errors can result in property damage personal injury or death Damages to this product due to improper wiring ARE...

Страница 17: ...LP 436 Rev 5 20 15 17 Figure 17 Wiring the Control...

Страница 18: ...nections been properly installed and are they leak free Is the water heater full of water Gas Connections Complete Is the gas supplied to the water heater the same type indicated on the water heater r...

Страница 19: ...ures at the hot water outlet Always remember to check the hot water coming out of any faucet with your hand before use This will reduce the risk of scalding related injury Figure 18 Thermostat D Out o...

Страница 20: ...erly refer to Drafthood Operation G Anode This water heater is equipped with multiple anode rods that are designed to prolong the life of the glass lined tank By the electrolytic action these anodes a...

Страница 21: ...ater follow these two easy steps 1 Consult the Troubleshooting Guide in this manual It will guide you to the most common problems experienced with a gas fired water heater The solutions you find liste...

Страница 22: ...019 16 Access Door 8800P 018 17 Outlet Nipple 8800P 032 18 Nipple Temperature and Pressure ReliefValve 8800P 033 8800P 034 19 Temperature and Pressure ReliefValve 8800P 035 8800P 036 20 Anode 8800P 03...

Страница 23: ...water heater The diagnostic system is designed to give the user or qualified service technician a visual indication of the operational status of the different parts of the water heater s control syste...

Страница 24: ...LP 436 Rev 5 20 15 24...

Страница 25: ...LP 436 Rev 5 20 15 25...

Страница 26: ...LP 436 Rev 5 20 15 26...

Страница 27: ...LP 436 Rev 5 20 15 27...

Страница 28: ...LP 436 Rev 5 20 15 28...

Страница 29: ...OXIDE DETECTORS At the time of installation of the side wall horizontal vented gas fueled equipment the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an...

Страница 30: ...TING SYSTEM PROVIDED When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment the instruct...

Страница 31: ...at optimum efficiency 2 Maintain all related heating components in good operating condition 3 Use the water heater in an open system with a properly sized and installed thermal expansion tank 4 Use th...

Страница 32: ...is denied If all warranty conditions are satisfied HTP will provide replacement parts to the retailer For questions about the coverage of this warranty please contact HTP at the address or phone numbe...

Страница 33: ...LP 436 Rev 5 20 15 33 Maintenance Notes...

Страница 34: ...f Installation Installation Address Product Name Serial Number s Comments Installer s Code Name Installers Phone Number Signed by Installer Signed by Customer Installation Notes IMPORTANT Customer Ple...

Отзывы: