76
LP-185 Rev. 9.9.14
BOILER START-UP REPORT
LIGHT OFF ACTIVITIES
DATE COMPLETED ________________
1) Fill the
heating system
Check all piping and gas connections, verify all
are tight
Pressurize system (12-15 PSI)
____ PSI
Add water to prime condensate hose
What percentage of propylene glycol is
installed in the system (0-50%)
____ %
Verify near boiler piping is properly supported
2) Check gas
pipe
Leak test using locally approved methods
(consult jurisdictional code book)
Check incoming gas pressure (3.5” to 14”
W.C.)
____ in w.c.
Static
What
is the “drop” on light off (No more than 1”
W.C.)
____ in w.c.
Dynamic
3) Check
combustion
Check and adjust (if necessary) carbon
dioxide content
____% CO2
High Fire
____% CO2
Low Fire
Check and adjust (if necessary) carbon
monoxide content
____ppm CO
High Fire
____ ppm CO
Low Fire
4) Verify
system
operation
Turn up thermostat to verify wiring connections
5) Record
ionization
current
Check uA reading at d7 on the status menu
(see start-up section)
____ uA
High Fire
____ uA
Low Fire
6) Record
system settings
Record heating curve (with optional Vision
One kit, record steps)
____*8
____*9
____*10
____*11
7) Indirect
water boiler
Verify safety and operation of the indirect
water heater, record settings
____de
____dh
8) Convert the
boiler
If necessary, convert the boiler to the proper
gas type
Locate the stickers in the appropriate locations
on the boiler
Verify combustion settings after gas
conversion, Carbon Dioxide
____% CO2
High Fire
____% CO2
Low Fire
Verify combustion settings after gas
conversion, Carbon Monoxide
____ppm CO
High Fire
____ppm CO
Low Fire
Mail in the conversion registration
Notes:
Table 19
MAINTENANCE REPORT
In unusually dirty or dusty conditions, care must be taken to keep boiler cabinet door in place at all times. Failure to do so VOIDS
WARRANTY!
Allowing the boiler to operate with a dirty combustion chamber will hurt operation. Failure to clean the heat exchanger as needed by the
installation location could result in boiler failure, property damage, personal injury, or death. Such product failures ARE NOT covered
under warranty.
The boiler requires minimal periodic maintenance under normal conditions. However, in unusually dirty or dusty conditions, periodic
vacuuming of the cover to maintain visibility of the display and indicators is recommended.
Periodic maintenance should be performed once a year by a qualified service technician to assure that all the equipment is operating
safely and efficiently. The owner should make necessary arrangements with a qualified heating contractor for periodic maintenance of
the boiler. Installer must also inform the owner that the lack of proper care and maintenance of the boiler may result in a hazardous
condition.
Содержание 140M
Страница 12: ...12 LP 185 Rev 9 9 14 Figure 1 Dimensions T 50M T 80M 80M ...
Страница 13: ...13 LP 185 Rev 9 9 14 Figure 2 Dimensions 140M 199M 399M ...
Страница 48: ...48 LP 185 Rev 9 9 14 I DIAGRAMS FOR SIDEWALL VENTING Figure 25 Venting ...
Страница 49: ...49 LP 185 Rev 9 9 14 Figure 26 Sidewall Venting ...
Страница 50: ...50 LP 185 Rev 9 9 14 J DIAGRAMS FOR VERTICAL VENTING Figure 27 Vertical Venting ...
Страница 55: ...55 LP 185 Rev 9 9 14 Figure 29 ...
Страница 70: ...70 LP 185 Rev 9 9 14 Figure 31 ...
Страница 71: ...71 LP 185 Rev 9 9 14 Figure 32 ...
Страница 72: ...72 LP 185 Rev 9 9 14 Figure 33 ...
Страница 73: ...73 LP 185 Rev 9 9 14 Figure 34 ...
Страница 74: ...74 LP 185 Rev 9 9 14 Figure 35 ...
Страница 75: ...75 LP 185 Rev 9 9 14 Figure 36 ...
Страница 78: ...78 LP 185 Rev 9 9 14 ...
Страница 79: ...79 LP 185 Rev 9 9 14 ...
Страница 80: ...80 LP 185 Rev 9 9 14 MAINTENANCE NOTES ...