O
PERATING
Y
OUR
B
OILER (continued)
PAGE 44
______________________________________________________________________________________________________________________________________________________________________________________
REGULAR STOKING OF THE BOILER (continued)
If The Draft Fan is
OFF
: (BOILER TEMPERATURE BELOW 140
°
F)
NOTE:
When the boiler temperature is below 140
°
F the assumption is that the fire has burned out
and that hot gases are not present. However, never quickly open the door unless you
have tried to vent hot gases from the firebox first.
1. Open the by-pass damper.
2. Turn the reset switch off and back on to activate the draft fan. Let the fan run for 2
minutes.
3. Turn off the fan by switching the reset switch off.
4. Immediately open the loading door ¾” with your left hand.
5. Wait approximately 20 seconds before opening the load door slowly, cautiously and fully.
6. If there are sufficient live coals left in the firebox to re-ignite the next load of wood you
will not need to use paper to restart the fire. Place several pieces of dry kindling in the
center of the firebox over the slot in the refractory and rake the live coals from the sides
of the firebox to the center on top of the kindling.
7. Add enough firewood to carry the estimated heat load for the next 8 hours as per the
“Operational Procedures” on page 45 which are very important.
8. Close the load door and immediately turn “ON” the draft fan switch (F). Close and latch
the by-pass by pushing in and down forcefully so that the spring will keep it closed.
9. HOWEVER, if you find very few live coals left in the firebox after opening the load door in
step #3 above, follow steps #3-#9 on page 40 to restart the fire.
If The Draft Fan Is
ON
:
1. Open the by-pass damper.
2. WAIT, 2-3 minutes with the draft fan running.
3. Turn off the draft fan by using the power switch on the control panel.
4. Without delay, open the loading door 3/4” with your left hand.
5. Wait approximately 20 seconds.
6. Open the loading door slowly, fully, and cautiously!
7. Load the firebox if the previous load has burned down to low coals, placing the wood
uniformly front to back and tight together, not crosswise.
8. Close the loading door.
9. Turn the draft fan back on by switching the power switch “ON” on the control panel.
10. Close the by-pass damper.
HEAT DEMAND ON THE BOILER
In order to achieve the best combustion efficiency and the longest boiler life with the least
amount of creosote in the combustion chamber, it is necessary that there be a reasonable
demand for heat when the boiler is operating on wood.
44
Содержание 2000
Страница 1: ......
Страница 4: ......
Страница 8: ... Intentionally left blank PAGE 4 4 ...
Страница 13: ...FEATURES AND SPECIFICATIONS PAGE 9 9 ...
Страница 28: ...FIELD WIRING DIAGRAMS PAGE 24 ...
Страница 29: ...24 WIRING SCHEMATIC FOR CONTROLS PAGE 25 ...
Страница 30: ...This is an insert page 25 ...
Страница 63: ...TARM EXCEL CAUTION LABEL PAGE 58 58 ...
Страница 65: ...BOILER Parts List PAGE 60 60 ...
Страница 66: ...BOILER Parts List PAGE 61 61 ...