O
PERATING
Y
OUR
B
OILER (continued)
PAGE 39
WOOD–BURNING OPERATIONS WITH HS-TARM EXCEL BOILERS
CHECK LIST:
1. PRIOR TO STARTING A WOOD FIRE, CHECK THE FOLLOWING THINGS:
a. Check the By-Pass Damper:
-
Is the damper plate in place on the actuator arm? To check this you will need to remove the
boiler's top jacket covers and remove the cleanout cover over the heat exchanger tubes.
-
Is the damper linkage adjusted properly (see page 28)
b. Check the Combustion Draft Fan:
-
Check operation of fan.
-
Make sure the fan air intake screen is clean and unobstructed.
-
Check the air damper operation (see page 41).
-
Check the primary air stop adjustment (see page 41).
-
Set the secondary air adjustment knob in the middle position (see page 41 & 42).
c. Check the settings on the L8124C, L6081A and L8151A aquastats (see page 35) and adjust to
the recommended values.
d. Check the Low Temperature Flue Gas Sensor setting (see page 34). Adjust if necessary.
e. Check the adjustments of the Balancing Valve (see page 32). It should be 50% closed.
2. OPERATING THE HS-TARM EXCEL BOILER :
a. Follow the instructions on pages 40 through 50 in the Installation and Operation Manual.