HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice
Page 10 of 33
Function Block Objects & Sub-Parameters
The following is an overview of the function block features and options. For in-depth description of
function choices and their use please also download or request the separate
FUNCPROG Application
Tool
document.
Function Block
Object
Para #
Description
Selection Options
Digital Input 1…4
1…4
x00=
x01=
x02=
Buttons 1…4, input type
Output OR
Output AND
7 - Digital, 14 - n/c, 15 - Toggle on/off
Object #
Object #
Digital Input 5…8
5…8
x00=7
Navigation buttons
Fixed, dedicated to Up, Down, Right, Left
respectively
Digital Output 1…6
Parameters 00…05:
©
Parameters 06…09:
Available on all versions
9…14
(x)x00=
(x)x01=
(x)x02=
(x)x03=
(x)x04=
(x)x05=
(x)x06=
(x)x07=
(x)x08=
(x)x09=
OR1
OR2
AND
PWM cycle time (sec)
ON
OFF
Minimum ON time (sec)
Minimum OFF time (sec)
Maximum Run time (sec)
Remember last state at power return
Object #
Object #
Object #
0…255
% of control loop demand
% of control loop demand
0…255
0…255
0…1000
0 - Disable, 1 Enable
LED 1 & 2
(Digital Output 7…8)
15…16
(x)x00=
(x)x01=
(x)x02=
(x)x03=
(x)x04=
(x)x05=
(x)x06=
(x)x07=
(x)x08=
(x)x09=
OR1
OR2
AND
PWM cycle time (sec)
ON
OFF
Minimum ON time (sec)
Minimum OFF time (sec)
Maximum Run time (sec)
Remember last state at power return
Object #
Object #
Object #
0…255
% of control loop demand
% of control loop demand
0…255
0…255
0…1000
0 - Disable, 1 Enable
Universal Input 1
17
1700=5
Fixed NTC 10k internal
5 - 10k NTC (-10…90°C)
[Ctx]
Universal Input 2
18
1800=
Sensor type
5 - 10k NTC (-10…90°C)
[Ctx]
7 - DI
[D]
14 – DI n/c
[DNC]
15 - Toggle on/off
[D T]
Universal Input 3…4
19…20
xx00=
Sensor type
0 - 100k NTC (-10…90°C)
[Ctc]
2 - 0-10Vdc (0…100%)
[%V1]
3 - 4…20mA (0…100%)
[%mA]
5 - 10k NTC (-10…90°C)
[Ctx]
7 - DI
[D]
8 - % (0-100%)
[%]
9 - Seconds
[Sec]
14 - Digital normally-closed
[DNC]
15 - Toggle on/off
[D T]
Common settings of UI 1…4
xx01=
Input calibration - Offsets the
measured value up to 10% of the
sensor range
Any value within 10% of the sensor range
xx02=
Filter incoming sensor measurement
when the connected sensor is
unstable
0 - Minimum (factory default)
1…9 - User setting where 9 represents
the maximum filtering sample time
For unstable sensors then a setting of 1
or 2 will typically be enough filtering to
result in a stable measurement
xx03=
xx04=
Output OR*
Output AND*
Object #
Object #
* Digital 1 = 1000 (100%) when applied to these analogue logic functions. Analogue values will act as a
Output Minimum when applied to an Output OR and Output Maximum when applied to an Output AND.