HRW HPD0460BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice
Page 12 of 33
Function Block
Object
Para #
Description
Selection Options
Network Interface
Objects (NIO)
105…112
xxx00=
xxx01=
xxx02=
xxx03=
xxx04=
xxx05=
xxx06=
xxx07=
Target node number
Object Instance type
Target Object Instance within target
node
Sensor type
Read/Write
Read-Value Scaling
Output OR *
Output AND *
Device # in the same network
0 - Disabled
1 - DI
2 - DV
3 - DO
4 - AI
5 - AV
6 - AO
1…65,535
Same as UI selection
0 = Read status of target Instance of
target node
1…112 = Write local Instance status to
target Instance of target node
0 – Normal (apply Sensor Type units
only), 1 - Raw (apply Sensor Type units,
intercept & scaling)
Object #
Object #
* Digital 1 = 1000 (100%) when applied to these analogue logic functions. Analogue values will act as a
Output Minimum when applied to an Output OR and Output Maximum when applied to an Output AND.
LED 3 & 4 and the audible beeper have a fixed 5sec PWM cycle time with 1sec resolution. Therefore
if digital 1 or 100% is applied then the LED/beeper will be on continuously. If 60% applied then the
LED/beeper will be on for 3sec, off 2sec, on 3sec, and so on. The minimum applied value for an output
reaction is 20% (1sec on, 4sec off). In HPD0460BN these outputs may be driven by peer-to-peer
controllers on the network or via the internal NIO’s reading in object values from other controllers on the
network. HPD0460BNC, T or CT can control objects 25…27 directly using their own internal function
blocks.