Troubleshooting 55
Off
On
Off
On—Batt
ery
capacity
<25%
On—Batt
ery
capacity
>25%
On—Batt
ery
capacity
>50%
On—Batt
ery
capacity
>75%
Flashing
Overload condition (on page
)—UPS power capacity is
exceeded while on battery
with no other faults
Off
On
Off
Off
Off
Off
Flashing Flashing
Overload condition (on page
)—UPS power capacity is
exceeded while on battery
with overtemperature fault
Off
Flashing Off
Flashing Flashing Flashing Flashing Flashing
Unit is powering down
Flashing Flashing Flashing Flashing Flashing Flashing Flashing Flashing
Checksum failure error (on
* This LED can be in any state.
For the location of individual LEDs, see "UPS front panel LED indicators (on page
)."
UPS is in Auto-Bypass mode
The UPS transfers from Operate mode (on page
) to Auto-Bypass when one of the following fault
conditions is detected:
•
Inverter AC over voltage
•
Inverter AC under voltage
•
Rectifier input over current
•
Inverter output over current
•
Inverter fault
•
Heat sink over temperature
•
Fan failure
•
Overload
The load is supported, but not protected while in Auto-Bypass mode.
Action
:
1.
If power management software is being used, check the log files to obtain specific error information
to help identify the problem.
For more information about the causes of a general fault condition, see the HPE Power Manager
user guide available for download from the Hewlett Packard Enterprise website
http://www.hpe.com/info/rackandpower
2.
Verify that no blockage of airflow to the front bezel and rear panel exists.
UPS is in Converter Off mode
Fault conditions cause the UPS to transfer to Converter Off mode from Standby mode (on page
) only.
If the UPS is powering the load, fault conditions cause the UPS to transfer to Auto-Bypass mode instead.
If a fault condition exist and the UPS is running in Auto-Bypass mode (on page
), press the Off button to
transfer the UPS to Converter Off mode.
The load is not supported while in Converter Off mode.
The following fault conditions trigger Converter Off mode:
•
Inverter AC over voltage
•
Inverter AC under voltage
Содержание R/T3000 G2
Страница 18: ...Installation 18 ...
Страница 26: ...Installation 26 4 Attach the chassis to the rack using the supplied screws Connecting the battery leads ...
Страница 27: ...Installation 27 Attaching the ERM front bezel ...
Страница 38: ...Installation 38 Installing the extension bars if included ...
Страница 39: ...Installation 39 Connecting and securing the power cords ...
Страница 71: ...Support and other resources 71 ...
Страница 72: ...Support and other resources 72 ...
Страница 79: ...Index 79 W website Hewlett Packard Enterprise 65 weight ERM 60 weight UPS 60 ...