Maintenance 49
4.
Unplug the UPS power cord.
5.
Disconnect the communications cable from the option card.
6.
Disconnect the ground bonding cable.
7.
Disconnect the REPO port.
8.
Unplug the load devices.
9.
Unplug the ERM connected to the UPS.
10.
Remove the UPS front bezel ("
11.
Disconnect the battery leads.
12.
Remove the UPS battery bracket.
13.
Remove the UPS battery modules.
14.
Remove the screws securing the UPS to the rack.
15.
Remove the UPS from the rack.
To replace the component, reverse the removal procedure.
Replacing the ERM
To remove the ERM:
1.
Switch the circuit breaker for any attached ERMs to the Off position.
2.
Unplug the ERM from the back of the UPS.
3.
Unplug the ERM from a second connected ERM.
4.
Remove the front bezel ("
) on the ERM that is being
replaced.
5.
Disconnect the battery leads.
6.
Remove the screws securing the ERM to the rack.
7.
Remove the ERM from the rack.
To replace the component, reverse the removal procedure.
Replacing the UPS option card
This component is hot-swappable and can be replaced without powering down the UPS.
1.
(optional) To replace the component with the UPS powered down, refer to "Powering down the UPS
(on page
)."
2.
Disconnect the communications cable from the option card.
Содержание R/T3000 G2
Страница 18: ...Installation 18 ...
Страница 26: ...Installation 26 4 Attach the chassis to the rack using the supplied screws Connecting the battery leads ...
Страница 27: ...Installation 27 Attaching the ERM front bezel ...
Страница 38: ...Installation 38 Installing the extension bars if included ...
Страница 39: ...Installation 39 Connecting and securing the power cords ...
Страница 71: ...Support and other resources 71 ...
Страница 72: ...Support and other resources 72 ...
Страница 79: ...Index 79 W website Hewlett Packard Enterprise 65 weight ERM 60 weight UPS 60 ...