UPS operations 43
Available settings Parameter
Associated LED Explanation (when LED is
illuminated)
127/240 Nom
Overtemperature
Nominal output voltage is 127 V for a low
voltage model and 240 V for a high voltage
model
Wiring fault setting
Wiring fault
Overload
Audible alarm will sound when ground is
missing or line and neutral connections are
reversed
NOTE:
For high voltage UPSs, the Site Wiring Fault function is disabled by default, but can
be manually enabled.
To change the UPS configuration parameters:
1.
Place the UPS in Configure mode (on page
).
The LEDs associated with the currently configured parameters illuminate. A flashing cursor indicates
where you are in the configuration process as you scroll through the available settings.
2.
Press the On button to scroll through the options. Each time the On button is pressed, the audible
alarm sounds.
3.
If the On button is pressed and the UPS does not respond, the UPS is in Operate mode (on page
). Start over with step 1.
4.
Press the Off button once to toggle the selected option on or off.
5.
Repeat steps 2 and 3 for each option.
6.
To save the configuration settings and exit Configure mode, press and hold the Test/Alarm Reset
button for 3 seconds.
NOTE:
Configure mode times out after 2 minutes of inactivity. If the Test/Alarm Reset button
has not been pressed, any new selections are not saved.
For the location of buttons, see "UPS front panel controls (on page
)."
For the location of LEDs, see "UPS front panel LED indicators (on page
)."
Initiating a self-test
To initiate a self-test, press and hold the Test/Alarm Reset button ("
" on page
for three seconds.
If the UPS detects a problem, the appropriate LED ("
UPS front panel LED indicators
illuminates and an audible alarm may sound.
For information on what to do if the self-test detects a problem, see "Troubleshooting (on page
)."
Silencing an audible alarm
To silence an alarm, press the Test/Alarm Reset button ("
IMPORTANT:
•
Although the audible alarm silences, the condition that caused the alarm to sound may still
exist.
•
If a utility power failure caused the alarm, the alarm silences after power is restored.
For information about audible alarm conditions, see "LED and audible alarm troubleshooting ("
)."
Содержание R/T3000 G2
Страница 18: ...Installation 18 ...
Страница 26: ...Installation 26 4 Attach the chassis to the rack using the supplied screws Connecting the battery leads ...
Страница 27: ...Installation 27 Attaching the ERM front bezel ...
Страница 38: ...Installation 38 Installing the extension bars if included ...
Страница 39: ...Installation 39 Connecting and securing the power cords ...
Страница 71: ...Support and other resources 71 ...
Страница 72: ...Support and other resources 72 ...
Страница 79: ...Index 79 W website Hewlett Packard Enterprise 65 weight ERM 60 weight UPS 60 ...