Nonoperating Temperature, Humidity, and Altitude
•
Temperature:
-22° to 140° F (-30° to 60° C)
◦
◦
Maximum rate of change: 36° F/hr (20° C/hr)
◦
Reasonable rate of change with noncondensing relative humidity during the transition
from warm to cold
•
Relative humidity: 10% to 85%, noncondensing
•
Altitude: 0 to 40,000 feet (0 to 12,000 meters)
Cooling Airflow Direction
Each enclosure includes its own forced-air cooling fans or blowers. Air flow for each enclosure
enters from the front of the modular cabinet and rack and exhausts at the rear.
Typical Acoustic Noise Emissions
70 dB(A) (sound pressure level at operator position)
Tested Electrostatic Immunity
•
Contact discharge: 8 KV
•
Air discharge: 20 KV
Calculating Specifications for Enclosure Combinations
Power and thermal calculations assume that each enclosure in the cabinet is fully populated.
The power and heat load is less when enclosures are not fully populated, such as a Fibre Channel
disk module with fewer disk drives.
AC current calculations assume that one PDU delivers all power. In normal operation, the power
is split equally between the two PDUs in the cabinet. However, calculate the power load to assume
delivery from only one PDU to allow the system to continue to operate if one of the two AC power
sources or PDUs fails.
“Example of Cabinet Load Calculations” (page 71)
lists the weight, power, and thermal calculations
for a 42U NS2100 commercial system with:
•
Four blade elements
•
Two VIO enclosures
•
Two SAS disk enclosures and two Storage CLIMs
•
50 SAS disk drives in two enclosures
•
Two rack-mounted system consoles with keyboard/monitor units
•
Two maintenance switches
For a total thermal load for a system with multiple cabinets, add the heat outputs for all the
cabinets in the system.
Table 6 Example of Cabinet Load Calculations
Heat (BTU/hour)
Power Consumption
(Watts)
Weight
Height
(U)
Quantity
Component
(kg)
(lbs)
Maximum
Typical
Maximum
Typical
Calculating Specifications for Enclosure Combinations
71
Содержание Integrity NonStop NS2100
Страница 48: ...Figure 11 Modular PDU Connections Without UPS 48 System Installation Specifications for NS2100 Systems ...
Страница 49: ...Figure 12 Modular PDU Connections With Single Phase UPS Power Distribution for NS2100 Systems 49 ...
Страница 52: ...Figure 14 Example of Bottom AC Power Feed Without UPS 52 System Installation Specifications for NS2100 Systems ...
Страница 53: ...Figure 15 Example of Top AC Power Feed Without UPS Power Distribution for NS2100 Systems 53 ...
Страница 55: ...Figure 17 Example of Bottom AC Power Feed With Single Phase UPS Power Distribution for NS2100 Systems 55 ...
Страница 91: ...Figure 30 Example 36U Configuration Without UPS and ERM Typical NS2100 Configurations 91 ...
Страница 107: ...System Down OSM Low Level Link 107 ...