NonStop System With a Rack-Mounted UPS
shows an example of a supported configuration in a NonStop system with the left PDUs
connected to one or more rack-mounted UPS, and the right PDUs connected directly to the utility
power. The rack-mounted UPS is connected to the utility power.
Figure 34 NonStop System With a Rack-Mounted UPS
When OSM detects that one power rail is running on UPS and the other power rail has lost power,
OSM logs an event indicating the beginning of the configured ride-through time period. OSM
monitors if AC power is restored before the ride-through period ends.
•
If AC Power is restored before the ride-through period ends, the ride-through countdown
terminates and OSM does not take further steps to prepare for an outage.
•
If AC Power is not restored before the ride-through periods ends, OSM broadcasts a
PFAIL_SHOUT
command to all processors (the processor running OSM being the last one
in the queue) to shut down the system ServerNet routers and processors. The
PFAIL_SHOUT
command enables disk writes for data that is in transit through controllers and disks to
complete.
Supported UPS Configurations
113
Содержание Integrity NonStop NS2100
Страница 48: ...Figure 11 Modular PDU Connections Without UPS 48 System Installation Specifications for NS2100 Systems ...
Страница 49: ...Figure 12 Modular PDU Connections With Single Phase UPS Power Distribution for NS2100 Systems 49 ...
Страница 52: ...Figure 14 Example of Bottom AC Power Feed Without UPS 52 System Installation Specifications for NS2100 Systems ...
Страница 53: ...Figure 15 Example of Top AC Power Feed Without UPS Power Distribution for NS2100 Systems 53 ...
Страница 55: ...Figure 17 Example of Bottom AC Power Feed With Single Phase UPS Power Distribution for NS2100 Systems 55 ...
Страница 91: ...Figure 30 Example 36U Configuration Without UPS and ERM Typical NS2100 Configurations 91 ...
Страница 107: ...System Down OSM Low Level Link 107 ...