Power and current specifications for each type of enclosure are:
Peak Inrush Current
(amps)
Maximum
Power
Consumption
(Watts)
Typical Power
Consumption
(Watts)
AC Power Lines
per Enclosure
1
Enclosure Type
NA
469 (8 GB)
275 (8 GB)
2
Blade element
486 (16 GB)
292 (16 GB)
501 (32 GB)
304 (32 GB)
30
326
262
2
VIO enclosure
-
225
135
2
DL380 G6 Storage
CLIM
-
205
123
2
DL380p Gen8 Storage
CLIM
-
200
130
2
DL380 G6 IP or Telco
CLIM
-
203
117
2
DL380p Gen8
Networking CLIM 5
copper ports (IP or
Telco)
-
210
123
2
DL380p Gen8
Networking CLIM 3
copper/2 optical ports
(IP or Telco)
5
125
75
2
M8381-25 SAS disk
enclosure (no disks)
NA
9
5
NA
SAS disk drive 10k
rpm
NA
7
4
NA
SAS disk drive 15k
rpm
1.5 A (5 volts)
5.84
5.7
NA
Solid state drive, 200
GB
1.0 A (12 volts)
115
105
1
Rack-mounted system
console (NSCR210 or
NSCR212)
2
28
28
1
Rack-mounted
keyboard and monitor
4
20
20
1
Maintenance switch
(Ethernet)
2
1
One of the plugs for an enclosure must be connected to one of the left-side extension bars and the other one connected
to one of the right-side extension bars. PDUs must be supplied from separate branch circuits.
2
Maintenance switch has only one plug. If a UPS is installed in the modular cabinet, the maintenance switch plug must
be connected to the extension bars on the right side of the modular cabinet.
AC Input Power for Modular Cabinets
61
Содержание Integrity NonStop NS2100
Страница 48: ...Figure 11 Modular PDU Connections Without UPS 48 System Installation Specifications for NS2100 Systems ...
Страница 49: ...Figure 12 Modular PDU Connections With Single Phase UPS Power Distribution for NS2100 Systems 49 ...
Страница 52: ...Figure 14 Example of Bottom AC Power Feed Without UPS 52 System Installation Specifications for NS2100 Systems ...
Страница 53: ...Figure 15 Example of Top AC Power Feed Without UPS Power Distribution for NS2100 Systems 53 ...
Страница 55: ...Figure 17 Example of Bottom AC Power Feed With Single Phase UPS Power Distribution for NS2100 Systems 55 ...
Страница 91: ...Figure 30 Example 36U Configuration Without UPS and ERM Typical NS2100 Configurations 91 ...
Страница 107: ...System Down OSM Low Level Link 107 ...