Configuration parameters 54
When the utility power is lost, the example UPS behaves as follows:
1.
On load segment 1:
a.
Client1—The UPS Network Module waits until t2 to start OST. The server is powered down before
t3.
b.
Client2—The UPS Network Module waits until t2 to start OST. The server is powered down
sometime t3.
c.
UPS Network Module—The UPS Network Module waits until t2 to send shutdown commands to
load segment 1 and all Clients. Load segment 1 powers down at t3.
2.
On load segment 2:
a.
Client3—Because the OST of this Client is the longest, it replaced the OST of the UPS Network
Module after it was connected to the UPS Network Module. Client 3 powers down as configured.
b.
Client4—Because the SIA of the UPS Network Module is less than that of Client 4, the UPS Network
Module starts the shutdown process first. Client 4 is forced to start its OST at the same time.
c.
UPS Network Module—The UPS Network Module waits until t2 to initiate the shutdown sequence
for load segment 2 and the other Clients. Load segment 2 powers down at a new t3 which is the
same as the longest Client OST.
3.
UPS—Between the two OST of UPS Network Module on load segment 1 and load segment 2, the UPS
starts its countdown at t2 of UPS Network Module on load segment 2, because it received the shutdown
command from it first and then powered down at t3 of UPS Network Module on load segment 2 also
because it ends last.
When the utility power is restored, the example UPS behaves as follows:
1.
t5—If the Battery capacity exceeds condition exists, the UPS is powered on.
2.
t6 and t7—If the Switch On after condition exists, the LS is powered on.
3.
If Automatic Power ON is enabled in the BIOS setup of the Client server, the server will be powered on
as soon as power is detected.
Содержание UPS Network Module
Страница 60: ...Firewall configuration 60 13 Click Change scope to add more security to the port exception ...
Страница 63: ...Firewall configuration 63 ...
Страница 68: ...Alert messages 68 UPS Site Wiring Fault UPS Site Wiring Fault Cleared ...
Страница 82: ...Regulatory compliance notices 82 Class B equipment BSMI notice ...