HP UPS Network Module web interface 26
o
Delayed, safe power down & reboot
—A sequence containing a shutdown command followed by a
restart command for the load segment is launched when the Off Delay time is reached. Connected
equipment powers off, and then the load segment powers off. The load segment restarts when the
Toggle Duration time is reached.
o
Delayed On
—A restart sequence for the load segment is launched when the On Delay is reached.
The load segment powers on, and then connected equipment powers on.
2.
Configure the Off Delay time for delayed power down commands. Enter the number of seconds that
should elapse between the time you execute the command and the shutdown sequence initiates.
3.
Configure the Toggle Delay time for power down & restart commands. Enter the number of seconds that
should elapse between the time the shutdown sequence completes and the restart sequence initiates.
4.
Configure the On Delay time for power on commands. Enter the number of seconds that should elapse
between the time you execute the command and the restart sequence initiates.
5.
Click
Save
to save the Off Delay, Toggle Delay, and On Delay parameters.
6.
Click
Execute
to initiate the configured commands.
Click
Help
to view online help.
Schedule Shutdown screen
Click
Schedule Shutdown
in the menu tree to display the Schedule Shutdown screen. This screen allows an
administrator to optimize power consumption by configuring a weekly shutdown and restart schedule for the
UPS and connected equipment. To prevent data loss, configure the time required to shut down each
registered server using the Shutdown Parameters screen (on page
35
).
IMPORTANT:
When configuring a scheduled shutdown and restart on the same day, be sure
that the Restart Time is later than the Shutoff Time.
NOTE:
In a redundant configuration, do not set both UPS Network Modules to shut down at the
same time. Set the Shutoff Times 30 minutes apart so that HP Power Protector can perform a
graceful shutdown.
Содержание UPS Network Module
Страница 60: ...Firewall configuration 60 13 Click Change scope to add more security to the port exception ...
Страница 63: ...Firewall configuration 63 ...
Страница 68: ...Alert messages 68 UPS Site Wiring Fault UPS Site Wiring Fault Cleared ...
Страница 82: ...Regulatory compliance notices 82 Class B equipment BSMI notice ...