Branch circuit breaker specifications
4 poles, 32/40 A
Power cable specifications
Configuration
3 lines + N + PE
Minimum cross-sectional area
6 mm² or 10 AWG
Terminals
Ferrule terminals, except the PE terminal, which uses the M8 ring type
External diameter range
18.0–25.0 mm
Configuration 2: 200–240 V line-to-line three-phase configuration
Printer specifications
Number of power wires)
3 lines + PE
Input voltage (line to line)
200–240V (±10%)
Input frequency
50/60 Hz
Power consumption (typical)
9–11 kW
Maximum load current (per phase)
48 A (up to 60 A repetitive peak current)
Branch circuit breaker specifications
3 poles, 50/60 A
Power cable specifications
Configuration
3 lines + PE
Minimum cross-sectional area
10 mm² or 6 AWG
Terminals
Ferrule terminals, except the PE terminal, which uses the M8 ring type
External diameter range
18.0–25.0 mm
Power cables
No power cable is provided with the printer. The cables that you use must meet the minimum specifications for
the chosen configuration explained for each configuration, and must follow local laws. The example below is for
configuration 2.
ENWW
Printer electrical configuration