Installing Core Switch 2/64 FRUs
125
Core Switch 2/64 V4.1 Installation Guide
Display Failed Components
Use
errShow
to display the switch error log. The error log lists the status of
marginal/failed components. The following example shows that the Switch 0
blower assembly has failed.
sw0_155:admin> errshow
Error 15
--------
0x2e3 (fabos): Dec 29 15:57:34
Switch: 0, Error FW-BELOW1, 3, envFan001 (Env Fan 1) is below
low boundary. current value : 0 RPM. (faulty)