6.11 Supply air and extract air silencers
Supply air and extract air silencers reduce the noise from RoofVent
®
units within
the room. The supply air silencer is designed as a separated component and is
installed above the Air-Injector. The extract air silencer consists of acoustic insula-
tion lining in the connection module.
500
Size
6
9
Weight
kg
53
80
Supply air pressure drop
Pa
22
26
Extract air pressure drop
Pa
0
0
Table 21: Technical data of the supply air and extract air silencers
6.12 Hydraulic assembly diverting system
An assembly for the hydraulic diverting system is included in the delivery. It
consists of the following components:
■
Automatic air vent
■
Coil screw joint
■
Control valve
■
Distributor circuit screw joint
■
Flow
■
Mixing valve
■
Ball valve
■
Return
6.13 Mixing valve
Mixing valves which are optimally matched to the units are available for easy
installation of RoofVent
®
units. They have the following specifications:
■
3-way mixing valve with modulating rotary actuator (run time 9 s)
■
Flow characteristic:
–
Equal percentage control path
–
Linear bypass
■
Integrated position control and response
6.14 Condensate pump
The condensate pump is installed directly under the condensate drain connection;
the supplied container is prepared for installation on the Air-Injector. It pumps
the condensate through a flexible hose to a delivery head of 3 m, thus enabling
discharge of the condensate
■
through waste water pipes directly below the ceiling,
■
onto the roof.
RoofVent
®
RH | RC | RHC | R
Options
Art.No. 4 214 745-en-04 / Page 27