Assembling the below-roof unit
The below-roof unit must only be assembled at the building site if it must be deliv-
ered in multiple parts due to the unit version. Proceed as follows:
■
Make sure that the correct unit components match up (observe the unit number
and RoofVent
®
serial number).
■
Loosen the cable fastening on the connection module frame.
■
Screw in the transport eyes into the connection module frame and attach the
lifting gear.
■
Lift the connection module (if applicable, with the heating/cooling part mounted)
and rotate it into the correct position.
–
The standard position of the coil connections is underneath the extract air
grille. If another orientation is required, you can mount the heating or cooling
section turned round on the connection module.
Notice
Never change the orientation of the supply air silencer (option) relating
to the component above it. The correct position is marked on the unit.
■
Place the connection module on the bottom part.
■
Screw the components together; use the supplied screws and protective plugs
to do so.
Connection module
Heating section
Cooling section
Supply air silencer (option)
Air-Injector
Fig. 15: The components of the below-roof unit vary
depending on unit type.
Unit number
Type plate with serial number
(behind the access door)
Serial number
Fig. 16:
Identification of the unit components
8x
Fig. 17: Transport eye in
the connection module
Fig. 18: Below-roof unit screw connection with M6 x 20 screws and protective plugs (8
per component)
Fig. 19: Correct orientation of the supply air silencer:
For size 6: Sound attenuation splitters cross to coil connection side (or to the extract air grille for unit type R)
For size 9: Sound attenuation splitters parallel to coil connection side (or to the extract air grille for unit type R)
RoofVent
®
RH | RC | RHC | R
Transport and installation
Art.No. 4 214 745-en-04 / Page 33