background image

 

IMPORTANT 

The Clean Air Act of 1990 bans the intentional 
venting of refrigerant (CFC’s and HFC’s) as of 
July1, 1992. Approved methods of reclaiming must 
be followed. Fines and/or incarceration may be 
levied for non-compliance. 

 

 

 

 

WARNING! 

Product contains fiberglass wool. 
Disturbing the insulation in this product during 
installation, maintenance or repair will expose you 
to fiberglass wool. This material may cause 
respiratory, skin, and eye irritant. Breathing this 
may cause lung cancer. (Fiberglass wool is known 
to the State of California to cause cancer.) 
 

 

 

 

T

ABLE OF 

C

ONTENTS

 

Condensate Drain  3 

Refrigerant Charging Instructions 3 

Wiring Low Voltage Connections 5 

Physical Data, Nomenclature  6-7 

Electrical Wiring Diagram  9 

 Dimensions  10 

 

W SERIES AIR HANDLER  

WALL MOUNT INSTALLATION INSTRUCTIONS 

 

 
 

 
 

G

ENERAL                                                                                                                                        

 

These instructions are intended as a general guide and do 
not supersede local codes in any way. Consult with 
authorities having jurisdiction before installation. 
ADP “

W”

 series air handlers are suitable for closet or flush 

mount installations and are designed for electrical heat 
installation with a matched remote outdoor unit. These units 
are designed for indoor installations only. 

 
The following words are used throughout this manual to 
identify levels of hazard seriousness. 

DANGER

-Immediate hazards that WILL result in severe 

personal injury or death. 

WARNING

-Hazards or unsafe practices COULD result in 

severe personal injury or death. 

CAUTION

-Hazards or unsafe practices COULD result in 

minor personal injury or product or property damage. 
 
 

Part # 065463808  

October 2009 

 

 

R

ECEIVING

 

Check equipment for shipping  damage. If you find any 
damage, immediately contact the last carrier. 
Check the unit rating plate for unit size, electric heat, coil, 
voltage, phase etc. to be sure unit matches requirements. 

R

EQUIREMENTS

 

Installation of air handler units with or without optional 
electric heat must conform with standards in the National 
Fire Protection Association (NFPA) “Standard for 
installation of Air Conditioning and Ventilation Systems 
NFPA No. 90A,” and Standard for Installation of Residence 
Type warm Air Heating and Air Conditioning Systems NFPA 
No. 90B, manufacturer’s installation instructions and local 
municipal building codes. 
 
This unit is certified for installation clearances to 
combustible material as listed on the unit rating plate. 
Accessibility and service clearances must take precedence 
over combustible material clearances. 

 

   

    

 

DISCONTINUED

Содержание W 18

Страница 1: ...ese units are designed for indoor installations only The following words are used throughout this manual to identify levels of hazard seriousness DANGER Immediate hazards that WILL result in severe personal injury or death WARNING Hazards or unsafe practices COULD result in severe personal injury or death CAUTION Hazards or unsafe practices COULD result in minor personal injury or product or prope...

Страница 2: ... level and square before proceeding Attach brace in the upright position across the top of the unit refer to drawing DUCTWORK Ductwork should be fabricated and installed in accordance with local and or national codes This includes the standards of the National Fire Protection Association for installation of Air Conditioning and Ventilating Systems NFPA No 90B REFRIGERANT PIPING Refrigerant connect...

Страница 3: ...rge in heating mode is acceptable if necessary When charging Heat Pumps in the heating mode please refer to the outdoor unit s charging instructions FIXED ORIFICE 1 Run system for at least 10 minutes to allow pressure to stabilize 2 Add or recover refrigerant until the superheat matches the table below Outdoor Air Temp F Superheat F Min Nom Max 60 28 31 34 65 25 28 31 70 22 25 28 75 20 22 25 80 16...

Страница 4: ...ructions for installation procedures Run this drain to a place in compliance with local installation codes where it will be noticed when unit is operational Condensate flowing from the secondary drain indicates a plugged primary drain Prime the trap with water Test line for leaks Test water flow with unit in operation WIRING WARNING USE COPPER CONDUCTORS ONLY WARNING Run 24V Class 11 wiring only t...

Страница 5: ...ack to no heat a no heat reversion package is required for operation See ADP s Air Handler Accessories Sheet for further details BLOWER SPEED CHANGES From the factory the blower is set on medium speed blue To change to high black or low red remove the blue wire from the number 2 port and replace it with the black or red wire depending on your desired speed setting Low Voltage Connections Thermosta...

Страница 6: ...erant Conn IDS Suction 7 8 Refrigerant Conn IDS Liquid 3 8 3 8 3 8 3 8 3 8 3 8 Florator Piston Size 53 59 67 67 73 80 Weights Approx lbs 99 101 103 118 118 121 AIR HANDLER MAINTENANCE AT THE BEGINNING OF EACH HEATING SEASON THE UNIT SHOULD BE SERVICED BY A QUALIFIED INSTALLER OR SERVICING AGENCY ASSISTANCE OR SERVICE IF YOU NEED FURTHER ASSISTANCE YOU MAY CONTACT US AT THE ADDRESS BELOW OR E MAIL ...

Страница 7: ...mber Expansion Device 2 Florator 3 Bleed A C Expansion Valve R 22 4 Non Bleed A C Expansion Valve R 22 5 Non Bleed HP Expansion Valve R 22 6 Non Bleed A C Expansion Valve R410a 9 Non Bleed HP Expansion Valve R410a Nominal BTUH Cooling 18 18 000 24 24 000 etc Amount of Heat 00 0 Kw 05 5 Kw 07 7 5 Kw etc Disconnect or line voltage connection 0 5 7 5 10 12 5 15 Standard Optional S2 Stripped Wire P2 P...

Страница 8: ...ata Kw Mbtuh 1 240 V 1 240 V 208 V 240 V 208 V 240 V Circuit 1 Circuit 2 18 No Heat 0 0 1 2 1 1 1 5 1 4 15 18 Elec Heat 5 0 17 065 1 2 1 1 24 1 27 4 30 18 Elec Heat 7 5 25 598 1 2 1 1 35 3 40 4 45 18 Elec Heat 10 0 34 130 1 2 1 1 46 6 53 5 60 24 No Heat 0 0 2 1 9 2 5 2 4 15 24 Elec Heat 5 0 17 065 2 1 9 25 1 28 4 30 24 Elec Heat 7 5 25 598 2 1 9 36 3 41 4 45 24 Elec Heat 10 0 34 130 2 1 9 47 6 54 ...

Страница 9: ...ELECTRICAL WIRING DIAGRAM 9 D I S C O N T I N U E D ...

Страница 10: ... X 14 0 W 31 36 42 18 3 4 44 1 2 14 1 2 7 3 8 6 0 2 1 2 5 1 2 12 0 D X 14 0 W Internal View Of Bottom Of Air Handler Drain Pan Side Drain Conn Line Voltage F A 22 12 B Primary Secondary Top View C D 1 3 8 3 0 G Duct Opening 3 4 Front 8 1 2 8 1 2 E 2 Suction Liquid Low Voltage 10 D I S C O N T I N U E D ...

Страница 11: ... if the ADP product is removed from the original installation site This warranty does not apply to damage caused by shipping misuse mishandling or damage caused by floods winds fires lightning or exposure to corrosive elements environments such as salt chlorine fluorine or other damaging chemicals Limitations of Warranty The costs of refrigerant refrigerant reclamation miscellaneous material and l...

Страница 12: ...D I S C O N T I N U E D ...

Отзывы: