background image

TECHNICAL BULLETIN 2019-

0008

Date:  

0

6

/

03

/201

9

 

Subject:  

Multi-Position Air Handler 

M

odels:  

AC0**KNZDCH

/AA

AM0**

T

NZDCH/AA

, AM0**JNZDCH/AA

 

www.SamsungHVAC.com     TB201

9

-000

8

 (REV 7/8/2020)

1

Multi-Position Air Handler Blower Troubleshooting

© 20

20

 Samsung HVAC

Multi

-

position air handlers use a Genteq X13 constant torque blower motor.

  

Below are the steps that can 

be used to troubleshoot the motor if a problem is suspected.

The motor rocks back and forth on start up. 

This is normal operation. 

 

Genteq X13 constant torque blower motors have a rotor position circuit-built in. 

 

At start 

up, the motor rocks forward then backward to determine which direction it needs to turn for proper airflow. 

 

Do 

not remove the motor from the blower wheel and housing to test. 

 

Without a blower wheel attached, the motor 

will not be able to tell which direction to run. 

 

It will simply rock back and forth.

Airflow is insufficient

Make sure there are no restrictions to airflow such as dirty or restrictive air filters, closed dampers or registers, dirty 
indoor coil or blower wheel. 

 

Ensure the airflow settings are set properly by measuring total external static 

pressure and adjusting fan motor speed taps as needed. 

 

Refer to the service manual for blower performance 

charts that will show airflow for each speed tap at given static pressures.

Motor does not run

Genteq X13 constant torque blower motors should be supplied line voltage between L & N on the motor 
connector at all times even when there is no call for operation. 

 

Check for line voltage directly at the L & N 

connection of the motor

.

Samsung HVAC maintains a policy of ongoing development, specifications are subject to change without notice.  

230 VAC 

Отзывы: