10
4 214 864 / 02
ASSEMbly
2.4
Installation of the cladding and boiler
controller
1.
Hook the right side walls (10.x, Fig. 07) on the angle
rail (see detail A).
2. Hook the left side walls (11.x) on the angle rail (see
detail A).
3. Route the condensate drain hose (12) through the
side wall.
4. Hook the rear walls (13.1/13.2) onto the folded edges
of the side wall (10.2/11.2).
- CompactGas (2800-4200):
6 folded edges of side wall
5. Route the burner cable (14) with the burner connec-
tion plug (14a) through the prepared bore hole (14b)
in the side wall.
- The burner must be connected to the boiler with the
standard plug connection.
- The burner cable must be installed so that the plug
connection has to be disconnected in order to swing
out the burner.
6.
Mount the boiler controller (15) and wire up the im
-
mersion sensor (16) and burner cable (14), see chap-
ter “2.4.1 Installation of boiler controller”, page 12.
!
WARNING
Capillaries must not be folded or kinked
7. Insert 2 insulating mats (17.1/17.2) (to prevent ver
-
tical circulation of air) longitudinally on the left and
right.
8.
Mount cladding covers (18.1/18.2/18.3) (note the or
-
der).
9. Attach C-clips (19) to the top of the front side walls
(10.1/11.1).
10. Installing cladding covers (20):
- Position cladding covers.
- Secure cladding cover with 2 self-tapping screws
Ø 4.8 x 50 (see detail B).
- Align the cladding cover using the height-adjustable
bracket (21).
11. Installing door cladding:
- Fasten 4 or 8 threaded bolts (22) with nut and two
washers to the boiler door (see detail C).
- Push insulating mats (23.1/23.2) onto the boiler
door.
-
Cut a recess for the burner flange out of the insulat
-
ing mat (23.3).
To achieve continuous thermal insulation be-
tween the boiler front and burner, the recess
in the insulating mat (23.3) must have the size
and shape of the burner flange.
- Push the insulating mat (23.3) into the recess be-
tween the insulating mats (23.1/23.2).
- Install door cladding (24 or 24.1/24.2).
- CompactGas (1800-4200):
First install lower part of the 2-part door cladding.
12.
Affix number plate and, where applicable, mount
manual holder (25) on the side.
13. Install side shutter, see “2.4.2 Installation of side shut-