Dimensions BioLyt (50 & 70)
BioLyt
Type
L
H1
H2
H3
B1
B2
B3
B4
E1
E2
E3
(50)
1660 2218 1705 1545 740 640 105 175 1310 490 1290
(70)
1685 2298 1800 1635 800 740 200 190 1410 590 1385
1
Minimum distance to wall on the control panel side
700mm, on opposite side 150mm
Measurements and space requirements for maintenance
(all measurements in mm)
1a
Boiler flow connection
R 1¼"
1b
System flow connection
R 1¼“
2a
Boiler return conection
R 1¼"
2b
System return connection
R 1¼“
3a
Pellet feed system / transfer box / RAS 51
3b
Optional RAS 41 pellet transportation
∅
50 mm
system centrifugal separator
4
Safety heat exchanger connections
2 x R ½"
5
Drain
R ¾"
6
Flue gas outlet
external Ø 150 mm
7
Induced draught fan
8
Control panel (can be fitted right or left side)
9
Sight glass
10
Pocket for boiler sensor
(behind the casing)
Rp ¾"
11
Pocket for sensor of the thermal
flow safeguard (behind the casing)
Rp ½"
12
Low return temperature protection kit
H1 less 273 mm if RAS centrifugal separator fitted (3b above)
3
Hoval BioLyt (50-160)