Page 32
electrical Requirements
Prodigy
®
(Model H) and Jetsetter
®
(Model JJ)
230 volt converted models
ImporTanT!
The exact physical location of the terminals on the gFcI
breaker will vary between manufacturers. connecting the hot wire to the neutral
terminal will cause irreversible damage to the control box.
*AVAIlABle FRoM deAleR.
ImporTanT:
All WIRINg SHould Be coPPeR.
NoTe: The wire connections to gFcI breakers are for reference only. Always ensure the white neutral wire is connected to the load neutral of the 20 amp breaker.
** Refer to Nec 250-122 (table)
WIRINg coNNecTIoNS
ImporTanT:
Fill the spa with water before turning on the power
•
once your spa has been filled with water, turn it on and test all the
circuit breakers.
each breaker should be tested prior to each use. Here’s how:
1. Push the “TeST” button on each gFcI breaker, and observe it click
off.
2. Wait 30 seconds, then push the breaker switch to the oFF (down)
position (to ensure that it has completely disengaged), then push the
breaker switch to the oN (up) position. If you don't wait 30 seconds,
the spa’s power indicator may continue to blink – try again.
If any of the gFcI breakers fails to operate in this manner, your spa
may have an electrical malfunction, and you may be risking electrical
shock. Turn off all circuits and do not use the spa until the problem has
been corrected by an authorized service agent.
ImporTanT:
Service Technician must reconfigure spa using the soft
jumpers to allow spa heater to run concurrent with jet pump.
Содержание ARIA AR
Страница 1: ...H i g h l i f e C o l l e c t i o n...
Страница 41: ......
Страница 42: ......
Страница 43: ......