94
6. REMOVAL AND REPLACEMENT OF HOT GAS VALVE AND LINE
VALVE
CAUTION
Always use a copper tube of the same diameter and length when replacing
the hot gas lines; otherwise the performance may be reduced.
IMPORTANT
Always install a new Drier every time the sealed refrigeration system is
opened. Do not replace the Drier until after all other repair or replacement
has been made.
1) Turn off the power supply.
2) Remove the panels.
3) Recover the refrigerant and store it in an approved container.
4) Remove the screw and the Solenoid.
5) Disconnect the Hot Gas Valve or Line Valve using brazing equipment.
6) Install the new valve.
WARNING
Always protect the valve body by using a damp cloth to prevent the valve
from overheating. Do not braze with the valve body exceeding 250°F.
7) Install the new Drier.
8) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
9) Evacuate the system, and charge it with refrigerant. For air-cooled and water-
cooled models, see the Nameplate for the required refrigerant charge. For remote
air-cooled models, see the Charge Label in the machine compartment.
Содержание KML "F" SERIES
Страница 6: ...6 I SPECIFICATIONS 1 KML 250MAH...
Страница 7: ...7 2 KML 250MWH...
Страница 8: ...8 3 KML 350MAF...
Страница 9: ...9 4 KML 350MWF...
Страница 10: ...10 5 KML 350MAH...
Страница 11: ...11 6 KML 350MWH Beginning serial L00001J ending Serial M20060C...
Страница 12: ...12 7 KML 350MWH Beginning serial M30061E...
Страница 13: ...13 8 KML 450MAF...
Страница 14: ...14 9 KML 450MWF...
Страница 15: ...15 10 KML 450MAH...
Страница 16: ...16 11 KML 450MWH Beginning Serial L00001D ending Serial M10530B...
Страница 17: ...17 12 KML 450MWH Beginning Serial M20531D...
Страница 18: ...18 13 KML 600MAF...
Страница 19: ...19 14 KML 600MWF...
Страница 20: ...20 15 KML 600MRF...
Страница 21: ...21 16 KML 600MAH...
Страница 22: ...22 17 KML 600MWH Beginning Serial L00001D ending Serial M10115C...
Страница 23: ...23 18 KML 600MWH Beginning Serial M10121E...
Страница 24: ...24 19 KML 600MRH...
Страница 25: ...25 20 CONDENSER UNIT URC 7F Unit mm inches...
Страница 26: ...26 SPECIFICATIONS URC 7F...
Страница 48: ...48 b KML 250MWH KML 350MWF KML 350MWH KML 450MWF KML 450MWH KML 600MWF KML 600MWH...
Страница 49: ...49 c KML 600MRF KML 600MRH...
Страница 65: ...65 4 PERFORMANCE DATA a KML 250MAH...
Страница 66: ...66 b KML 250MWH...
Страница 67: ...67 c KML 350MAF...
Страница 68: ...68 d KML 350MWF...
Страница 69: ...69 e KML 350MAH...
Страница 70: ...70 f KML 350MWH Serial L00001J through M20060C...
Страница 71: ...71 g KML 350MWH Beginning Serial M30061E...
Страница 72: ...72 h KML 450MAF...
Страница 73: ...73 i KML 450MWF...
Страница 74: ...74 j KML 450MAH...
Страница 75: ...75 k KML 450MWH Serial L00001D through M10530B...
Страница 76: ...76 l KML 450MWH Beginning Serial M20531D...
Страница 77: ...77 m KML 600MAF...
Страница 78: ...78 n KML 600MWF...
Страница 79: ...79 o KML 600MRF...
Страница 80: ...80 p KML 600MAH...
Страница 81: ...81 q KML 600MWH Serial L00001D through Serial M10115C...
Страница 82: ...82 r KML 600MWH Beginning Serial M10121E...
Страница 83: ...83 s KML 600MRH...