33
2) Defrost Timer
The defrost cycle starts when the Float Switch opens and completes the freeze cycle.
But the Defrost Timer does not start counting until the Thermistor senses 48°F at the
Evaporator outlet. The period from the end of the freeze cycle up to the point of the
Thermistor's sensing varies depending on the ambient and water temperatures.
3) High Temperature Safety - 127 ± 7°F
The temperature of the suction line in the refrigerant circuit is limited by the High
Temperature Safety.
During the defrost cycle the Evaporator temperature rises. The Thermistor senses
48°F and starts the Defrost Timer. After the Defrost Timer counts down to zero,
the normal freeze cycle begins. If the Evaporator temperature continues to rise,
the Thermistor will sense the rise in temperature and at 127 ± 7°F the Thermistor
operates the High Temperature Safety.
This High Temperature Safety shuts down the circuit and the icemaker automatically
stops. To reset the safety, turn the power off and back on again.
This High Temperature Safety protects the unit from excessive temperature. The Control
Board will Beep every 3 seconds. The white Reset Button on the Control Board must be
pressed with power on to reset the Safety.
4) Low Water Safety
If the Pump Motor is operated without water, the mechanical seal can fail. To prevent this
type of failure, the Controller Board checks the position of the Float Switch at the end of
the initial one minute water fill cycle and at the end of each defrost cycle.
If the Float Switch is in the up position (electrical circuit closed), the Controller Board
changes to the ice making cycle. If the Float Switch is in the down position (electrical
circuit open), the Controller Board changes to a one minute water fill cycle before starting
the ice making cycle. This method allows for a Low Water Safety shut down to protect
the Water Pump from mechanical seal failure.
For water-cooled model, if the water is shut off, the unit is protected by the High Pressure
Switch.
5) High Voltage Cutout
The maximum allowable supply voltage of this icemaker is limited by the High Voltage Cutout.
If miswiring (especially on single phase 3 wire models) causes excessive voltage on the
Controller Board, the High Voltage Cutout shuts down the circuit in 3 seconds and the icemaker
automatically stops. When the proper supply voltage is resumed, the icemaker automatically
starts running again. The Control Board will signal this problem using 7 Beeps every 3 seconds.
6) LED Lights and Audible Alarm Safeties
The red LED indicates proper control voltage and will remain on unless a control voltage
problem occurs. At startup a 5 second delay occurs while the board conducts an internal
timer check. A short beep occurs when the power switch is turned ON or OFF.
Содержание KML "F" SERIES
Страница 6: ...6 I SPECIFICATIONS 1 KML 250MAH...
Страница 7: ...7 2 KML 250MWH...
Страница 8: ...8 3 KML 350MAF...
Страница 9: ...9 4 KML 350MWF...
Страница 10: ...10 5 KML 350MAH...
Страница 11: ...11 6 KML 350MWH Beginning serial L00001J ending Serial M20060C...
Страница 12: ...12 7 KML 350MWH Beginning serial M30061E...
Страница 13: ...13 8 KML 450MAF...
Страница 14: ...14 9 KML 450MWF...
Страница 15: ...15 10 KML 450MAH...
Страница 16: ...16 11 KML 450MWH Beginning Serial L00001D ending Serial M10530B...
Страница 17: ...17 12 KML 450MWH Beginning Serial M20531D...
Страница 18: ...18 13 KML 600MAF...
Страница 19: ...19 14 KML 600MWF...
Страница 20: ...20 15 KML 600MRF...
Страница 21: ...21 16 KML 600MAH...
Страница 22: ...22 17 KML 600MWH Beginning Serial L00001D ending Serial M10115C...
Страница 23: ...23 18 KML 600MWH Beginning Serial M10121E...
Страница 24: ...24 19 KML 600MRH...
Страница 25: ...25 20 CONDENSER UNIT URC 7F Unit mm inches...
Страница 26: ...26 SPECIFICATIONS URC 7F...
Страница 48: ...48 b KML 250MWH KML 350MWF KML 350MWH KML 450MWF KML 450MWH KML 600MWF KML 600MWH...
Страница 49: ...49 c KML 600MRF KML 600MRH...
Страница 65: ...65 4 PERFORMANCE DATA a KML 250MAH...
Страница 66: ...66 b KML 250MWH...
Страница 67: ...67 c KML 350MAF...
Страница 68: ...68 d KML 350MWF...
Страница 69: ...69 e KML 350MAH...
Страница 70: ...70 f KML 350MWH Serial L00001J through M20060C...
Страница 71: ...71 g KML 350MWH Beginning Serial M30061E...
Страница 72: ...72 h KML 450MAF...
Страница 73: ...73 i KML 450MWF...
Страница 74: ...74 j KML 450MAH...
Страница 75: ...75 k KML 450MWH Serial L00001D through M10530B...
Страница 76: ...76 l KML 450MWH Beginning Serial M20531D...
Страница 77: ...77 m KML 600MAF...
Страница 78: ...78 n KML 600MWF...
Страница 79: ...79 o KML 600MRF...
Страница 80: ...80 p KML 600MAH...
Страница 81: ...81 q KML 600MWH Serial L00001D through Serial M10115C...
Страница 82: ...82 r KML 600MWH Beginning Serial M10121E...
Страница 83: ...83 s KML 600MRH...