20
a)
Freeze Cycle Diagnosis
: Confirm Comp, FMR, and PM continue. Confirm that
FM and LLV energize. Confirm WRV opens. Next, confirm HGV and X10 relay
de-energize. During the first 5 min. of freeze, confirm evaporator is cooling. If not,
confirm WV de-energized (not leaking by), HGV de-energized (not bypassing), LLV
and FM energize, TXV and HM operate correctly, WRV opens, Comp is efficient,
and refrigerant charge is correct. See "VIII.A. Specification and Performance Data
Sheets."
b)
Comp and FMR Diagnosis
: If Comp and FMR de-energize once freeze begins,
check that appliance has not shut off on HPS (CB "POWER OK" LED off). If so,
check "3)b) HPS Diagnosis" above. If CB "POWER OK" LED is on, check for 115VAC
at CB K1 #1 (V) or #9 (V) to neutral (W). If 115VAC is not present and LED 1 is on,
replace CB. If 115VAC is present, check for 115VAC at CR coil. If 115VAC is present,
check CR coil and contact continuity. Replace as needed. If CR is okay, check Comp
start relay and start and run capacitors. Next, check Comp motor winding continuity.
If Comp is energized but evaporator is not cooling, check for an inefficient Comp.
See "VIII.A. Specification and Performance Data Sheets." If Comp is energized but
FMR is not, check for 115VAC at the FMR junction box. If 115VAC is not present,
check icemaker wiring connections. If 115VAC is present, check for voltage at
condenser unit. If 115VAC is not present, check field wiring connections. If 115VAC is
present, check FMR capacitor, motor winding, and fan blade for binding.
c)
WV and HGV Diagnosis
: If WV is energized, check for 115VAC at CB K1 #6 (O)
to neutral (W). If 115VAC is present after PM energizes in harvest cycle, replace
CB. If 115VAC is not present, replace WV (bypassing). If HGV did not de-energize
at the end of harvest, check for 115VAC at CB K1 #2 (P) to neutral (W). If 115VAC
is present and LED 3 is off, replace CB. If 115VAC is not present, replace HGV
(bypassing).
d)
PM Diagnosis
: Confirm water is flowing over evaporator from PM and not WV. If PM
de-energizes once freeze begins, check for 115VAC at CB K1 #4 (R) to neutral (W).
If 115VAC is not present, replace CB. If 115VAC is present and PM is de-energized,
check for 115VAC at control switch #5 (W/R) to neutral (W). If 115VAC is present at
CB K1 #4 (R) and not at control switch #5 (W/R), check control switch continuity
between #5 (W/R) and #4 (R). Replace as needed. If 115VAC is present at control
switch #5 (W/R) to neutral (W), check PM capacitor and motor winding continuity.
e)
FM and LLV Diagnosis
: If FM or LLV does not energize, check for 115VAC at CB
K1 #3 (BK) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present:
For FM, check capacitor, motor winding, and blade for binding.
For LLV, check coil voltage and continuity.