34
Low Ice Production - Possible Cause
9. Compressor
a) Inefficient or off.
10. Liquid Line Valve
a) Erratic or open.
11. Thermostatic Expansion Valve
a) Defective.
Long Freeze Cycle
1. Evaporator
a) Scaled up, dirty.
2. Float Switch
See "II.F. Float Switch Check and
Cleaning"
a) Scaled up, dirty.
b) Float sticking.
c) Defective switch.
3. Inlet Water Valve
a) Leaking by.
4. Hot Gas Valve
a) Erratic or open.
5. Condenser
a) Clogged.
6. Control Board
See "II.D. Control Board Check"
a) Float switch connection loose (K5).
b) Defective.
7. Refrigerant Charge
a) Low.
8. Thermostatic Expansion Valve
a) Bulb loose.
b) Defective.
9. Compressor
a) Inefficient or off.
10. Pump Motor
a) RPM too slow.
11. Liquid Line Valve
a) Erratic or restricted.
12. Headmaster (C.P.R.)
(remote models)
a) Not bypassing.
13. Splash Guard
a) Out of place.
b) Missing or damaged.
Freeze-Time Correction Cycle Initiated
1. Evaporator
a) Scaled up, dirty.
2. Float Switch
See "II.F. Float Switch Check and
Cleaning"
a) Scaled up, dirty.
b) Float sticking.
c) Defective switch.
3. Refrigerant Charge
a) Low.
4. Splash Guard
a) Out of place.
b) Missing or damaged.
5. Distribution/Spray Tubes
a) Scaled up, dirty.
6. Cube Guides
a) Out of position.
b) Damaged.
7. See "2. Freeze Up" Above