25
Alarm Signals
Alarm
Code
No. of Beeps
(every 10 sec.) Problem
Reset Options
CF
1
Clogged Filter Alarm
Condenser temperature is outside of
normal operating range.
Air filter and/or condenser require
cleaning.
NOTICE!
If this alarm occurs
frequently, discharge temperature is
consistently too high. Failure to take
action could result in
damage to the compressor.
Clean the air filter and/or condenser.
Allow time for the sensor to reset,
then press the "RESET" button.
During alarm, press the "RESET"
button to silence the alarm for
2 hours.
If this alarm occurs frequently, call a
qualified service technician.
door
2
Door Alarm
Display Only: Door open.
Both Display and Beeps: Door open
longer than 3 minutes.
Close the door. During alarm, press
the "RESET"button to silence the
alarm for 3 minutes.
I. Cooling Performance
Be sure the appliance is properly installed and located for optimum cooling performance.
If cooling performance is not at its optimum level, check the following items:
• Door(s) opened too often.
• Door(s) left open. Close.
• Too packed with food or cabinet air inlet/outlet blocked. Allow some space between items/
containers to ensure good air flow.
• Warm or hot foods inside. Take them out until they cool down more.
• Ambient temperature too high. Avoid installation near high heat producing equipment or
exposure to direct sunlight.
• Cabinet temperature setting too high. Readjust it to a lower temperature.
• Appliance in defrost process. The cabinet temperature may rise temporarily during the
defrost cycle, but this will not affect the food inside.
J. Cabinet Condensation
In the event condensation develops on the cabinet exterior, check the following items:
• Perimeter frame heater off. Move the perimeter frame heater switch, located on the
control box, to the "ON" position (red marking visible).
• Door(s) left open, close.
• Ambient humidity too high. In high humidity areas it may be necessary to wipe off the
cabinet frame occasionally.