17
Startup/Cool Down
1. Check all wiring connections. Confirm the CTh is properly connected.
2. Energize the cooler.
3. Check for 115VAC to neutral (W). If 115VAC is not present, check the Power supply, wire
connections.
4. Check that cabinet temperature is displayed. If not, replace CM.
5. Make sure door is closed.
6. Check that Comp and ConFM energize. If not, check CTh status. See “Thermistor Check.”
If CTh ohm reading is in proper range, check for 115VAC at CM to neutral. If 115VAC is not
present, replace CM.
7. Defrost initiation. Defrost initiation at 4 hours of cumulative compressor run time
for 25-min. Confirm Comp and ConFM de-energize, EvapFM continues on. Check for
115VAC at CM to neutral for Comp and ConFM, then at CM to neutral for EvapFM. If
defrost indicator is on and 115VAC is present, replace CM.
8. Defrost termination, check after a 25 min. that the Comp energizes.
Legend
:
CM
–Control Module;
Comp
–compressor;
ConFM
–condenser fan motor;
CTh–
cabinet thermistor;
DS
–door switch;
DTh
–defrost thermistor;
EvapFM
–evaporator fan
motors,
MH
–mullion heater;
PH
–perimeter heater.
Содержание EF1A-FS
Страница 1: ...FREEZER Service Manual ER1A FS ER2A FS EF1A FS EF2A FS Issued 07 26 2019 Revised 07 14 2020...
Страница 28: ...28 Model Run Capacitor Starting Capacitor ER1A FS 15 F 250 V 250 F 160 V B Wiring Diagram...
Страница 29: ...29 Model Run Capacitor Starting Capacitor EF1A FS 10 F 250 V 150 F 160 V...
Страница 30: ...30 Model Run Capacitor Starting Capacitor ER2A FS 15 F 250 V 250 F 160 V...
Страница 31: ...31 Model Run Capacitor Starting Capacitor EF2A FS 30 F 250 V 200 F 160 V...
Страница 32: ...SERIES 618 Hwy 74 South Peachtree City GA 30269 USA P 800 227 3172 www economyseries com MAN 342 R...