1.8 Digital DC Outputs

Outputs per Module

12 Including 2 Configurable PWM Out-

puts and 1 Stepper

Commons per Module

1

Output Type

Sourcing / 10k

Ω

 Pull-Down

Absolute Max. Voltage

28VDC Max

Output Frequency

10kHz or 65kHz with HE-XHSQ

Output Protection

Short Circuit

Max. Output Current per Point

0.5A

Max. Total Current

4A Continuous

Max. Output Supply Voltage

30VDC

Min. Output Supply Voltage

10VDC

Max. Voltage Drop at Rated 
Current

0.25VDC

Max. Inrush Current

650mA per Channel

Min. Load

None

OFF to ON Response

1ms

ON to OFF Response

1ms

Output Characteristics

Current Sourcing (Pos. Logic)

PWM Out

 

≈ 

10kHz

Rise Time

50 - 115

μ

s

Fall Time

8 - 20

μ

s

Analog Inputs, High Resolution

Number of Channels

2

Input Ranges (Selectable)

0-10VDC; 0-20mA; 4-20mA; 

100mV; RTD: PT100; and 

J, K, N, T, E, R, S, B Thermocouples 

Safe Input Voltage Range

10VDC:  -0.5V to +15V 

20mA:  -0.5V to +6V 

RTD / T/ C:  +/- 24VDC

Nominal Resolution

10V, 20mA, 100mV:  14 Bits 

RTD, Thermocouple:  16 Bits

Input Impedance 
(Clamped @ -0.5VDC to 12VDC)

Current Mode: 

100

Ω

, 35mA Max. Continuous

Voltage Mode: 

500k

Ω

, 25mA Max. Continuous

%AI Full Scale

10V, 20mA, 100mV:  

32,000 counts full scale 

RTD / T/C:  20 Counts / 

˚

C

Max. Over-Current

35mA

Open Thermocouple Detec Current

50nA

Analog Inputs, High Resolution Continued

Thermocouple: 
B / R / S 
E
T
J
K / N

Temperature Range: 
32

˚

F  to 2,912

˚

F (0

˚

C to 1,600

˚

C)

-328

˚

F to 1,652

˚

F (-200

˚

C to 900

˚

C) 

-400

˚

F to 752

˚

F (-240

˚

C to 400

˚

C) 

-346

˚

F to 1,382

˚

F (-210

˚

C to 750

˚

C) 

-400

˚

F to 2,498

˚

F (-240

˚

C to 1, 370

˚

C)

Thermocouple Common Mode Range

+/- 10V

Converter Type

Delta Sigma

Max. Error at 25

˚

C  

(*excluding zero)

*4-20mA    +/- 0.10% of full scale 
*0-20mA    +/- 0.10% of full scale 
*0-10VDC    +/- 0.10% of full scale
RTD (PT100)  +/- 1.0°C

 

of full scale 

0-100mV    +/- 0.05% of full scale

Max. Thermocouple Error 
(After Warm up Time of One Hour)

 +/-0.2% (+/-0.3% below -100°C) 

of full scale

Conversion Speed,
Both Channels Converted

10V, 20mA, 100mV:  30 Times/Second 

RTD Thermocouple:  7.5 Times/Second

Conversion Time per Channel

10V, 20mA, 100mV:  16.7ms 

RTD, Thermocouple:  66.7ms

RTD Excitation Current

250

µ

A

1.9 Analog Inputs, High Resolution

1.7 Digital DC Inputs

Inputs per Module

12 Including 4 Configurable HSC Inputs

Commons per Module

1

Input Voltage Range

12VDC / 24VDC

Absolute Max. Voltage

30VDC Max.

Input Impedance

10k

Ω

Input Current

:

Positive Logic:

  

Negative Logic:

Upper Threshold 
Lower Threshold

0.8mA  
0.3mA

-1.6mA

-2.1mA

Max. Upper Threshold

8VDC

Min. Lower Threshold

3VDC

OFF to ON Response

1ms

ON to OFF Response

1ms

High Speed Counter 

Max Freq*

500kHz .

*See I/O info below for detail regarding HSC and PWM

  technical specifications continued...

Analog Inputs

Number of Channels

2

Output Ranges

0-10VDC 

0-20mA

Nominal Resolution

12 Bits

Update Rate

Once per PLC scan

Max. Error at 25°C 
(Excluding Zero)

0-20mA     0.1% of full scale
0-10V         0.1% of full scale

Analog Inputs

Minimum 10V Load

1k

Ω

Minimum Resistance Load

500

Ω

Analog Outputs; 
Output Points Required

2

Additional Error for Temp. Other 
than 25°C

20mA       0.000143%/C°
0-10V        0.000151%/C°

1.10 Analog Outputs

Содержание XLE Series

Страница 1: ...mulator Size 32 bits each Modes Supported Totalizer quadrature pulse measurement frequency measurement set point controlled outputs 1 6 High Speed Outputs Modes Supported Stepper PWM Output Frequency 10kHz or 65kHz with HE XHSQ 1 2 User Interface Display Type Transflective LCD Sunlight Readable Resolution 128 x 64 pixels XLE 160 x 128 pixels XLT Color Monochrome Built In Storage 16MB User Program ...

Страница 2: ...log Inputs High Resolution Continued Thermocouple B R S E T J K N Temperature Range 32 F to 2 912 F 0 C to 1 600 C 328 F to 1 652 F 200 C to 900 C 400 F to 752 F 240 C to 400 C 346 F to 1 382 F 210 C to 750 C 400 F to 2 498 F 240 C to 1 370 C Thermocouple Common Mode Range 10V Converter Type Delta Sigma Max Error at 25 C excluding zero 4 20mA 0 10 of full scale 0 20mA 0 10 of full scale 0 10VDC 0 ...

Страница 3: ...ings are required for Pos Neg setup When used as a normal input and not for high speed functions the state of the input is reflected in registers I1 I12 Digital inputs may alternately be specified for use with High Speed Counter functions also found in the Hardware Configuration for Digital Inputs Refer to the XLE XLT User Manual MAN0878 for full details Positive Logic vs Negative Logic Wiring The...

Страница 4: ...8 H1 I9 HSC1 Dig In 9 H2 I10 HSC2 Dig In 10 H3 I11 HSC3 Dig In 11 H4 I12 HSC4 Dig In 12 NC No Connect NC No Connect 0V Common I1 I2 I3 I4 I5 I6 I7 I8 HI H2 H3 H4 NC NC 0V 12 24VDC J2 Black Name 0V Common V V NC No Connect Q12 Q12 Digital Out 12 Q11 Q11 Digital Out 11 Q10 Q10 Digital Out 10 Q9 Q9 Digital Out 9 Q8 Q8 Digital Out 8 Q7 Q7 Digital Out 7 Q6 Q6 Digital Out 6 Q5 Q5 Digital Out 5 Q4 Q4 Dig...

Страница 5: ...ated at either end of the multidrop daisy chained RS 485 network DIP SWITCHES PIN NAME FUNCTION DEFAULT 1 MJ1 RS 485 Termination ON Terminated OFF 2 MJ2RS 485 Termination ON Terminated OFF 3 Bootload Always Off OFF 1 2 3 The I O is mapped into OCS Register space in three separate areas Digital Analog I O High Speed Counter I O and High Speed Output I O Digital Analog I O location is fixed starting...

Страница 6: ... Insert the XLE XLT through the panel cutout from the front The gasket must be between the host panel and the XLE XLT 5 Install and tighten the four mounting clips provided in the box until the gasket forms a tight seal NOTE Max torque 0 8 to 1 13 Nm or 7 10 in lbs 6 Reinstall the XLE XLT I O Removable Terminal Blocks Connect communications cables to the serial port USB ports Ethernet port and CAN...

Страница 7: ...tion is made to the module 1 Connect the safety earth ground on the power connector first before making any other connections 2 When connecting to the electric circuits or pulse initiating equipment open their related breakers 3 Do NOT make connection to live power lines 4 Make connections to the module first then connect to the circuit to be monitored 5 Route power wires in a safe manner in accor...

Отзывы: