page 5 of 7

installation continued on next page...

  4 COMMUNICATIONS

Solid/Stranded Wire

: 12-24 awg (2.5-0.2mm). 

Strip Length:

 0.28” (7mm).

Locking spring-clamp, two-terminators per conductor.

Torque, Terminal Hold-Down Screws:

 4.5 – 7 in-lbs (0.50 – 0.78 N-m). 

V+ pin is not internally connected, the SHLD pin is connected to Earth 
ground via a 1 M

Ω

 resistor and 10nF capacitor.

CAN Pin Assignments

PIN

SIGNAL

DESCRIPTION

1

V–

CAN Ground – Black

2

CN L

CAN Data Low – Blue

3

SHLD

Shield Ground – None

4

CN H

CAN Data High – White

5

V+ (NC)

No Connect – Red

4.1 - CAN Communications

MJ1 PINS

PIN SIGNAL

DIRECTION

8

TXD

OUT

7

RXD

IN

6

0V

GROUND

5

+5V @ 60mA OUT

4

RTS

OUT

3

CTS

IN

2

RX-/TX-

IN/OUT

1

RX+/TX+

IN/OUT

4.2 - Serial Communications

MJ1:

 RS-232

w/full handshaking or

 

RS-485 

half-duplex

RS-485 termination via switches; 

biasing via software

4.4 - Dip Switches

The DIP switches are used to provide a built-in termination to both the 
MJ1 port and MJ2 port if needed. The termination for these ports should 
only be used if this device is located at either end of the multidrop/daisy-
chained RS-485 network.

DIP SWITCHES

PIN NAME

FUNCTION

DEFAULT

1

MJ1 RS-485 
Termination

ON =  
Terminated

OFF

2

MJ2 RS-485 
Termination

ON =  
Terminated

OFF

3

Bootload

Always Off

OFF

 

1

 

2

 

3

The I/O is mapped into OCS Register space, in three separate areas 
Digital/Analog I/O, High-Speed Counter I/O, and High-Speed Output 
I/O. Digital/Analog I/O location is fixed starting at 1, but the high-speed 
counter and high-speed output references may be mapped to any open 
register location. For more details, see XLE/XLT OCS User’s Manual 
(MAN0878)

.

 

5  BUILT-IN I/O for Model 5

Digital and Analog I/O Function

Digital Inputs

%I1-12

Reserved

%I13-31

ESCP Alarm

%I32

Digital Outputs

%Q1-12

Reserved

%Q13-24

Analog Inputs

%AI1-2

Reserved

%AI3-12

Analog Outputs

%AQ9-10

Reserved

%AQ1-8

MJ2 PINS

PIN

SIGNAL

DIRECTION

8

232 TXD

OUT

7

232 RXD

IN

6

0V

Ground

5

+5V @ 60mA

OUT

4

485 TX-

OUT

3

485 TX+

OUT

2

485 RX- or RX/TX-

IN or IN/OUT

1

485 RX+ or RX/TX+

IN or IN/OUT

MJ2 SERIAL PORT 

MJ2: 

 RS-232 or RS-

485 half or full-duplex, 

software selectable

RS-485 termination 

via switches; biasing via 

software

4.3 - Ethernet Communications

Green LED indicates link – when illuminated, data 

communication is available. 

Yellow LED indicates activity – when flashing, data is 

in transmission

.

Wiring Details:

 

Solid/Stranded Wire:

  12-24 awg (2.5-0.2mm

2

). 

Strip Length: 

 0.28” (7mm).

Torque, Terminal Hold-Down Screws: 

 4.5 – 7 in-lbs (0.50 – 0.78 N-m).

Attach optional ferrite core with a minimum of two turns of serial cable.  
See website for more details. [Part #: HE-FBD001]

Содержание XLE Series

Страница 1: ...mulator Size 32 bits each Modes Supported Totalizer quadrature pulse measurement frequency measurement set point controlled outputs 1 6 High Speed Outputs Modes Supported Stepper PWM Output Frequency 10kHz or 65kHz with HE XHSQ 1 2 User Interface Display Type Transflective LCD Sunlight Readable Resolution 128 x 64 pixels XLE 160 x 128 pixels XLT Color Monochrome Built In Storage 16MB User Program ...

Страница 2: ...log Inputs High Resolution Continued Thermocouple B R S E T J K N Temperature Range 32 F to 2 912 F 0 C to 1 600 C 328 F to 1 652 F 200 C to 900 C 400 F to 752 F 240 C to 400 C 346 F to 1 382 F 210 C to 750 C 400 F to 2 498 F 240 C to 1 370 C Thermocouple Common Mode Range 10V Converter Type Delta Sigma Max Error at 25 C excluding zero 4 20mA 0 10 of full scale 0 20mA 0 10 of full scale 0 10VDC 0 ...

Страница 3: ...ings are required for Pos Neg setup When used as a normal input and not for high speed functions the state of the input is reflected in registers I1 I12 Digital inputs may alternately be specified for use with High Speed Counter functions also found in the Hardware Configuration for Digital Inputs Refer to the XLE XLT User Manual MAN0878 for full details Positive Logic vs Negative Logic Wiring The...

Страница 4: ...8 H1 I9 HSC1 Dig In 9 H2 I10 HSC2 Dig In 10 H3 I11 HSC3 Dig In 11 H4 I12 HSC4 Dig In 12 NC No Connect NC No Connect 0V Common I1 I2 I3 I4 I5 I6 I7 I8 HI H2 H3 H4 NC NC 0V 12 24VDC J2 Black Name 0V Common V V NC No Connect Q12 Q12 Digital Out 12 Q11 Q11 Digital Out 11 Q10 Q10 Digital Out 10 Q9 Q9 Digital Out 9 Q8 Q8 Digital Out 8 Q7 Q7 Digital Out 7 Q6 Q6 Digital Out 6 Q5 Q5 Digital Out 5 Q4 Q4 Dig...

Страница 5: ...ated at either end of the multidrop daisy chained RS 485 network DIP SWITCHES PIN NAME FUNCTION DEFAULT 1 MJ1 RS 485 Termination ON Terminated OFF 2 MJ2RS 485 Termination ON Terminated OFF 3 Bootload Always Off OFF 1 2 3 The I O is mapped into OCS Register space in three separate areas Digital Analog I O High Speed Counter I O and High Speed Output I O Digital Analog I O location is fixed starting...

Страница 6: ... Insert the XLE XLT through the panel cutout from the front The gasket must be between the host panel and the XLE XLT 5 Install and tighten the four mounting clips provided in the box until the gasket forms a tight seal NOTE Max torque 0 8 to 1 13 Nm or 7 10 in lbs 6 Reinstall the XLE XLT I O Removable Terminal Blocks Connect communications cables to the serial port USB ports Ethernet port and CAN...

Страница 7: ...tion is made to the module 1 Connect the safety earth ground on the power connector first before making any other connections 2 When connecting to the electric circuits or pulse initiating equipment open their related breakers 3 Do NOT make connection to live power lines 4 Make connections to the module first then connect to the circuit to be monitored 5 Route power wires in a safe manner in accor...

Отзывы: