MAN0922-01-EN                                                                                             SmarMod Quick Start Guide

 

 

____________________________________________________________________________________ 

Page 6 of 14                                                                                                                                         1017 

10.  Select Screens/View edit Screens (Figs. 6&7). 

 

 

Fig.6  

 

Содержание SmartMod HE359DIQ512

Страница 1: ...Introduction to SmartMod Step by Step Guide 1 Setting up and connecting an HE359DIQ512 to an XLt MJ2 port ...

Страница 2: ..._____________________________________________________________________ Page 2 of 14 1017 Cscape 1 Open Cscape and create a new program file 2 Select Program Protocol Configuration Fig 1 Fig 1 3 Select Modbus Master protocol from the dropdown list Fig 2 Fig 2 ...

Страница 3: ...SmarMod Quick Start Guide ____________________________________________________________________________________ Page 3 of 14 1017 4 Select Network button and setup Fig 3 Fig 3 5 Select Ok and then Select Device button ...

Страница 4: ...Page 4 of 14 1017 6 Setup the device Fig 4 Fig 4 1 A descriptive name for the attached device 2 Modbus ID for Smartmod 1 is correct for initial communication 3 5 digit Addressing for SmartMod 4 Enabling the Status register provides feedback see troubleshooting the connection below 7 Select Ok and then select Scan List button ...

Страница 5: ... Fig 5 1 Select device from drop down list Bracketed number indicates Node ID 2 Starting register Holding registers are appropriate 3 Up to 8 registers are required for the HE359DIQ512 4 The starting register R in the XLt where the data will be mapped 5 Polled Read Write as changes can be made to settings in the SmartMod 9 Select OK OK OK to return to Cscape main window ...

Страница 6: ...MAN0922 01 EN SmarMod Quick Start Guide ____________________________________________________________________________________ Page 6 of 14 1017 10 Select Screens View edit Screens Figs 6 7 Fig 6 ...

Страница 7: ...__ Page 7 of 14 1017 Fig 7 11 Select Numeric Data button then click and drag an area on the XLt screen Double click the field and set up the data Fig 8 Fig 8 12 Add a second similar data field to the screen Use Controller Register R0007 40007 SmartMod and use 3 digits Decimal Format Editable Fig 9 Fig 9 13 Download to XLt ...

Страница 8: ... Initialisation settings connect SmartMod Comm Port SmartMod Comm Port C GND D INIT 15 When the cable is assembled connect the RJ45 end to MJ2 on the XLt Connect the Smartmod 4 way terminal block to the HE359DIQ512 comm port 16 Power up the HE359DIQ512 SmartMod The Initialisation settings INIT connected to GND at power up will cause the SmartMod to start in the following mode Baud Rate 9600 No par...

Страница 9: ...artMod 18 Take note of the value displayed at 40006 and compare it to the following table Fig 11 to discern the actual communication settings in the unit Fig 11 19 For example a displayed value of 0000000001011111 would indicate the following Bits 0 2 added to give Baud Rate Bit 0 On decimal 1 Bit 1 On decimal 2 Bit 2 On decimal 4 The sum of these three bits gives a value of 7 indicating a Baud Ra...

Страница 10: ...___ Page 10 of 14 1017 21 Using the XLt touchscreen keypad edit the fields to suitable values for your application 22 Any changes that are made to the SmartMod settings MUST also be reflected in the Cscape XLt setup Otherwise communications may be lost when the INIT to GND connection is disconnected and the SmartMod reset ...

Страница 11: ... Generally used as an indicator that an excessive number of triggered transfers or failed communication retries are occurring that is lengthening the expected transaction scan time If the Update interval is set to zero update as fast as possible this 32 bit register alternately specifies the actual transaction scan time in mSec resolution No Response Count R1002 R1003 32 bit Number of times that a...

Страница 12: ...ablished and bad then expect to see the value in R1004 5 increase Check the cable connections and or register addressing in Cscape Protocol Configuratiuon Scanlist 5 If there is no communications then R1002 will increment Check cable is connected XLt and SmartMod are powered and configured and that the XLt is in RUN mode 6 For individual Modbus Nodes SmartMods another register can be enabled at Cs...

Страница 13: ...ic Modbus Node 129 Slave Timeout 130 Bad Checksum corrupted incoming data 131 No response 197 Slave does not support this function 198 PLC Reference type doesn t match data type 200 Specified data length exceeds Modbus frame size 8 All of the appropriate registers can be added and their values viewed live in Cscape when the XLt is connected by using the Controller Datawatch window Fig 14 Fig 14 ...

Страница 14: ...r Data Field SmartMod does not retain settings and will only communicate at 9600 baud Ensure GND and INIT jumper is disconnected No Communications between XLt and SmartMod Check cable Check SmartMod GND and INIT Pins are connected Power cycle SmartMod Check that Network Settings in Cscape Protocol configuration are appropriate Check program is downloaded to XLt Check cable is connected to MJ2 No c...