MAN0922-01-EN SmarMod Quick Start Guide
____________________________________________________________________________________
Page 14 of 14 1017
Other Checks
SmartMod PWR LED Off
Check power to SmartMod
SmartMod PWR LED not flashing
Has communication been established? Is
the Baud rate set for 9600 or lower?
Cannot edit data on Xlt screen
Ensure Editable box is ticked for Data
Field.
SmartMod does not retain settings and will
only communicate at 9600 baud
Ensure GND and INIT jumper is
disconnected.
No Communications between XLt and
SmartMod
Check cable. Check SmartMod GND and
INIT Pins are connected? Power cycle
SmartMod. Check that Network Settings in
Cscape/Protocol configuration are
appropriate. Check program is
downloaded to XLt. Check cable is
connected to MJ2
No communications between Cscape and
XLt
Check PC serial connection to MJ1. Check
Cscape Local and Target addresses are
identical. Ensure protocol configuration is
loaded to MJ2