7. This register value gives feedback for the specific Modbus Node.
•
129 - Slave Timeout
•
130 - Bad Checksum (corrupted incoming data)
•
131 - No response
•
197 - Slave does not support this function.
•
198 - PLC Reference type doesn't match data type
•
200 - Specified data length exceeds Modbus frame size
8. All of the appropriate registers can be added and their values viewed live in
Cscape when the XLt is connected by using the
Controller/Datawatch
window
(Fig. 14).
Fig. 14