Low-pressure water
refilling system
FNC
© 2012, Hoppecke Batterie Systeme GmbH, all rights reserved.
Appendix: Important aspects for proper filling
Procedure:
Repeated start-up of the filling operation may lead to the cells getting overfilled.
As soon as the waterfilling cart has shut down, all cells are completely filled.
Ensure that the waterfilling cart is connected to the proper power supply when
charging it.
While filling, the waterfilling cart should not be connected to the mains supply.
The waterfilling cart should be stored and operated only at temperatures > 0°C.
Installation:
Avoid the hose pipes from getting entangled since the flow rate would
otherwise get reduced. The hose pipes should not get twisted. If angles of 90°
are required, appropriate angular connectors must be used. Hose pipes of
different diameters should not be used on one battery.
Take care to see that all hose pipes fit securely on the connecting pieces of
the plugs and that the plugs are installed properly in the cells. Leakages
resulting from improper installation affect the proper working of the system and
lead to the cells getting overfilled and discharge of the electrolyte.