WEBVISION™
95-7769—01
150
Heat Cool Switch
X
X
X
Off or On
Heat Stages
X
X
X
Units=null
Precision=0
Min=0.0
Max=3.0
IO Test In
X
X
X
False or True
IO Test Switch
X
X
X
Off or On
Low Flow Alarm
X
X
X
False or True
Manual Occupancy
X
X
X
Default
Occupied
Unoccupied
Bypass
Standby
Mode
X
X
X
Startup Wait
Heat
Cool
Reheat
Morning Warm-up
Night Purge
Pressurize
Depressurize
Track Flow
Manual Position
Manual Flow
Freeze Protect
Factory Test
IO Test
Floating Out of Sync
Disabled
Manual
Model
X
X
X
Units=null
Precision=0
Min=0.0
Max=3.0
Monitor Switch
X
X
X
Off or On
Monitor Switch
X
X
X
Off or On
Occupancy Sensor
X
X
X
Unoccupied
Occupied
Override
X
X
X
Default
Occupied
Unoccupied
Bypass
Standby
Override IO
X
X
X
False or True
Peripheral Heat On
X
X
X
Off or On
Peripheral Heat Position
X
X
X
Units=%
Precision=1
Min=0.0
Max=100.0
Reheat Position
X
X
X
Units=%
Precision=1
Min=0.0
Max=100.0
Table 87. VAV II Application of Points (Continued)
Point Name
Graphics Alarms Trends Commandable Internal Use
Valid Values