WEBVISION™
95-7769—01
106
APPENDIX B – DEVICE POINT TABLES
This appendix provides a table for the points detail and a table
for the application of points of the following controllers and
devices:
• W7763C/D/E Chilled Ceiling Controller (CHC) .. page 106
• Constant Volume Air Handling Unit Controller
(CVAHU) ..............................................................page 114
• Fan Coil Unit Controller (FCU) ........................... page 122
• Hydronic Controller (HYD) ................................. page 129
• Excel 10 Remote Input/Output Device (RIO) ..... page 136
• Vacon NX Frequency Converter (NXVFD) ......... page 138
• T7350 Thermostat (T7350) ................................ page 138
• Unit Ventilator (UV) ............................................ page 138
• Excel 10 VAV II Controller (VAV II) ...................... page 145
• XL15C Plant Controller (XL15C) ......................... page 155
W7763C/D/E Chilled Ceiling
Controller (CHC)
Table 74 provides the CHC points detail and Table 75 on
page 107 provides the CHC application of points.
Table 74. CHC Point Details.
Point Name
Network Variable
Field Name
Point Type
Occupied Cool
nciSetPnts
occupiedCool
NumericWritable
Standby Cool
nciSetPnts
standbyCool
NumericWritable
Unoccupied Cool
nciSetPnts
unoccupiedCool
NumericWritable
Occupied Heat
nciSetPnts
occupiedHeat
NumericWritable
Standby Heat
nciSetPnts
standbyHeat
NumericWritable
Unoccupied Heat
nciSetPnts
unoccupiedHeat
NumericWritable
Current State
nviTodEvent
currentState
EnumWritable
Next State
nviTodEvent
nextState
EnumWritable
Time To Next State
nviTodEvent
timeToNextState
NumericWritable
DLC Shed
nviDlcShed
DlcShed
EnumWritable
Out Of Limits
nvoStatus
outOfLimits
BooleanPoint
Open Circuit
nvoStatus
openCircuit
BooleanPoint
Out Of Service
nvoStatus
outOfService
BooleanPoint
Mechanical Fault
nvoStatus
mechanicalFault
BooleanPoint
Feedback Failure
nvoStatus
feedbackFailure
BooleanPoint
Over Range
nvoStatus
overRange
BooleanPoint
Under Range
nvoStatus
underRange
BooleanPoint
Electrical Fault
nvoStatus
electricalFault
BooleanPoint
Unable To Measure
nvoStatus
unableToMeasure
BooleanPoint
Command Failure
nvoStatus
commFailure
BooleanPoint
Self Test Failed
nvoStatus
failSelfTest
BooleanPoint
Application Mode
nviApplicMode
hvacMode
EnumWritable
Fan Speed
nviFanSpeedCmd
SNVTSwitch
Manual Mode
nviRequest
objectRequest
EnumWritable
Manual Occupancy
nviManOccCmd
occupancy
EnumWritable
Temporary Setpoint
nviSetPoint
tempP
NumericWritable
Effective Setpoint
nvoChcStatus
activeSetPt
NumericPoint
Alarm Type
nvoChcStatus
alarmType
EnumPoint