WEBVISION™
123
95-7769—01
Fan Feedback
nvoFcuStatus
fanFeedback
NumericPoint
External Active
nvoFcuStatus
externalActive
NumericPoint
Fan Stages Active
nvoFcuStatus
fanStagesActive
EnumPoint
Output Position 0
nvoFcuStatus
outputPosition0
NumericPoint
Output Position 1
nvoFcuStatus
outputPosition1
NumericPoint
Reheat Active
nvoFcuStatus
reheatActive
EnumPoint
Effective Setpoint
nvoFcuStatus
activeSetPt
NumericPoint
Space Temperature
nvoFcuStatus
spaceTemp
NumericPoint
Reset Bypass Time
nvoFcuStatus
restBypassTime
NumericPoint
Unit Status Mode
nvoUnitStatus
mode
EnumPoint
Primary Heat Output
nvoUnitStatus
heatOutputPrimary
NumericPoint
Secondary Heat Output
nvoUnitStatus
heatOutputSecondary
NumericPoint
Cool Output
nvoUnitStatus
coolOutput
NumericPoint
Economizer Output
nvoUnitStatus
econOutput
NumericPoint
Fan Output
nvoUnitStatus
fanOutput
NumericPoint
In Alarm
nvoUnitStatus
inAlarm
NumericPoint
Terminal Load
nvoTerminalLoad
levPercent
NumericPoint
Manual Mode
nviManualMode
ManualMode
EnumPoint
Table 78. FCU Points Details (Continued)
Point Name
Network Variable
Field
Point Type
Table 79. FCU Application of Points
Point name
Graphics Alarms Trends Commandable Internal Use
Valid Values
Occupied Cool (Setpoint)
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
Standby Cool (Setpoint)
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
Unoccupied Cool (Setpoint)
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
Occupied Heat (Setpoint)
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
Standby Heat (Setpoint)
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
Unoccupied Heat (Setpoint)
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
Current State
X
Default
Occupied
Unoccupied
Bypass
Standby