68-0160

8

VR8345M

INSTALLATION

When working with an intermittent pilot ignition sys-

tem, go next to the Connect Pilot Gas Tubing section.
When installing on a hot surface or direct spark ignition
system, go to the Wiring section.

Fig. 4—Top view of gas control.

3. Square off and remove burrs from end of tubing.
4. Use the compression fitting supplied with this gas

control. Slip the fitting over the tubing and slide out of the
way.

NOTE: When replacing a gas control, cut off old compres-

sion fitting and replace with the new compression fitting
provided on the gas control. Never use the old compres-
sion fitting because it may not provide a gas-tight seal.

5. Push tubing into the pilot gas tapping on the outlet end

of the control until it bottoms. While holding tubing all the
way in, slide compression fitting into place, engage threads
and turn until finger tight. Then tighten one more turn with
wrench. Do not overtighten. Refer to Figs. 6 and 7.

6. Connect other end of tubing to pilot burner according

to pilot burner manufacturer instructions.

Fig. 6—Always use new compression fitting.

OUTLET
PRESSURE 
TAP

INLET

OUTLET

WIRING
TERMINALS (2)

INLET
PRESSURE TAP

PRESSURE REGULATOR
ADJUSTMENT (UNDER 
CAP SCREW)

CONVENIENCE
TERMINALS (2)
(OPTIONAL)

PILOT OUTLET

PILOT ADJUSTMENT
(UNDER CAP SCREW)

GAS CONTROL KNOB

M8436

MUST USE WIRE ADAPTER (NOT SHOWN) ON HSI OR DSI SYSTEM.

MUST USE PILOT PLUG (NOT SHOWN) ON HSI OR DSI SYSTEM.

1

2

1

2

Fig. 5—Proper use of wrench on gas control.

APPLY WRENCH 
FROM TOP OR 
BOTTOM OF GAS 
CONTROL TO 
EITHER SHADED AREA

M8562

CONNECT PILOT GAS TUBING (INTERMITTENT
PILOT IGNITION ONLY)

1. Remove the pilot gas seal (plug).
2. Cut tubing to desired length and bend as necessary for

routing to pilot burner.

CAUTION

1. Do not make sharp bends or deform the tubing.
2. Do not bend tubing at the gas control or pilot

burner after compression fitting has been tight-
ened because this can result in gas leakage at the
connection.

GAS CONTROL

TIGHTEN NUT ONE TURN
BEYOND FINGER TIGHT

FITTING BREAKS OFF AND CLINCHES 
TUBING AS NUT IS TIGHTENED

TO
BURNER

M3076A

Fig. 7—Remove pilot gas seal (plug) and install
pilot gas tube for intermittent pilot application on
VR8345.

M8441

PV

MV

PV

MV

OFF 

ON 

PILOT GAS 
TUBE

Содержание TRADELINE VR8345M

Страница 1: ...Works with virtually all residential equipment and all but the largest commercial equipment with a regulation capacity range of 30 000 to 415 000 Btuh natural gas 48 600 to 672 300 LP gas All adjustments and wiring connections accessible from top of control Straight through body pattern 1 8 in NPT inlet and outlet taps on top of gas control aid adjustment of gas pressure in problem installations 3...

Страница 2: ...conditions and some minor differences in performance can be expected if those conditions are changed MODEL VR8345M Universal Combination Gas Control AMBIENT TEMPERATURE RANGE 40 to 175 F 40 to 79 C BODY PATTERN Straight through REGULATOR TYPE Standard opening INLET X OUTLET SIZE 3 4 x 3 4 inch IGNITION ADAPTER Configures VR8345M to operate with direct spark or hot surface ignition ELECTRICAL RATIN...

Страница 3: ...ed service technician to re place the gas control Force or attempted repair can result in fire or explosion TABLE 3 VR8345 REPLACES THESE GAS CONTROLS Continued Replacement Gas Controls Universal Old Model No Manufacturer VR8200 VR8300 VR800 Replacement 36E36 304 DSI HSI WHITE RODGERS VR8205A2024 VR8305M3506 VR8450A4113 VR8345M4302a 36E36 304 IP WHITE RODGERS VR8204A2076 VR8304M3509 VR8440A3025 VR...

Страница 4: ...2024 VR8305M3506b VR8450A4113b VR8345M4302a b V8185A1001 HONEYWELL VR8205A2024 VR8305M3506 VR8450A4113 VR8345M4302a V8185A1019 HONEYWELL VR8205A2024 VR8305M3506 VR8450A4113 VR8345M4302a V8185A1035 HONEYWELL VR8205A2024 VR8305M3506 VR8450A4113 VR8345M4302a V8185B1009 HONEYWELL VR8205A2024 VR8305M3506 VR8450A4113 VR8345M4302a V8185B1017 HONEYWELL VR8205A2024 VR8305M3506 VR8450A4113 VR8345M4302a V824...

Страница 5: ...302e VR8440A2134 HONEYWELL VR8204A2076c VR8304M3509 VR8440A3025c VR8345M4302c VR8440A2142 HONEYWELL VR8204A2076 VR8304M3509 VR8440A3025 VR8345M4302 VR8440M1000 HONEYWELL VR8204A2076 VR8304M3509 VR8440A3025 VR8345M4302 VR8440M2008 HONEYWELL VR8204A2076 VR8304M3509 VR8440A3025 VR8345M4302 VR8440M2016 HONEYWELL VR8204A2076c VR8304M3509 VR8440A3025c VR8345M4302c VR8440M2024 HONEYWELL VR8204A2076 VR830...

Страница 6: ...with 1 8 in compression fitting part no 3934014 1 f Use with 3 4 in angle flange part no 393690 15 g Requires 1 2 in straight flange part no 393690 16 or an angle flange part no 393690 13 CAUTION Never apply a jumper across or short the valve coil terminals This can burn out the heat anticipator in the thermostat or damage the electronic intermit tent pilot IP module IMPORTANT These gas controls a...

Страница 7: ...tional Fuel Gas Code ANSI Z223 1 NFPA No 54 whichever applies Tubing installation must comply with approved standards and practices 1 Use new properly reamed pipe free from chips If tubing is used make sure the ends are square deburred and clean Make sure all tubing bends are smooth and without deformation 2 Run pipe or tubing to the gas control If tubing is used obtain a tube to pipe coupling to ...

Страница 8: ...ing to pilot burner manufacturer instructions Fig 6 Always use new compression fitting OUTLET PRESSURE TAP INLET OUTLET WIRING TERMINALS 2 INLET PRESSURE TAP PRESSURE REGULATOR ADJUSTMENT UNDER CAP SCREW CONVENIENCE TERMINALS 2 OPTIONAL PILOT OUTLET PILOT ADJUSTMENT UNDER CAP SCREW GAS CONTROL KNOB M8436 MUST USE WIRE ADAPTER NOT SHOWN ON HSI OR DSI SYSTEM MUST USE PILOT PLUG NOT SHOWN ON HSI OR D...

Страница 9: ...be in the valve pilot opening M8440 PV M V PV M V OFF ON PILOT GAS SEAL PLUG WIRE ADAPTER All wiring including insulated quick connect terminals mustcomplywithapplicableelectricalcodesandordinances 1 Check the power supply rating on the gas control and make sure it matches the available supply Install thermostat and other controls as required 2 When the gas control is installed on a hot surface or...

Страница 10: ...OR Q354 FLAME SENSOR LIMIT CONTROLLER THERMOSTAT OR CONTROLLER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED MAKE SURE L1 AND L2 ARE NOT REVERSED THIS WOULD PREVENT FLAME DETECTION ALTERNATE LIMIT CONTROLLER LOCATION SENSE TERMINAL AND Q354 FLAME SENSOR ON D MODELS ONLY BURNER GROUND M8563 QUICK CONNECTS AUTO IGNITION SYSTEMS ANSI Z21 20 STATUS LED 1 Flash Ignition Lock...

Страница 11: ...JURY OR DEATH Check for gas leaks with a rich soap and water solution anytime work is done on a gas control GAS LEAK TEST 1 Paint all pipe connections upstream of the gas control with a rich soap and water solution Bubbles indicate a gas leak 2 If a gas leak is detected tighten the pipe connection WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH 1 Donotforcethegasc...

Страница 12: ...CKING GAS INPUT BY CLOCKING THE GAS METER Make sure that the only gas flow through the meter is that of the appliance being checked Makecertainthatotherappliancesareturned off with pilot burners extinguished or de duct that gas consumption from the meter reading Convert the flow rate to Btuh as described in Gas Controls Handbook form 70 2602 and compare to the Btuh input rating on the appliance na...

Страница 13: ...programshouldincluderegularcheck out of the gas control see Startup and Checkout section To check out the control system see the appliance manufac turerliterature Maintenancefrequencymustbedetermined individually for each application Some considerations are Cycling frequency For appliances that may cycle 100 000 times annually check monthly Intermittent use For appliances that are used season ally...

Страница 14: ...lls for heat the DI module generates a spark at the main burner and the first automatic valve and second automatic valve operators are energized Fig 14 The first automatic valve opens and the second automatic valve operator valve disk is lifted off its seat This diverts gas flow from the second automatic valve diaphragm and causes a reduction of pressure on the underside of this diaphragm The redu...

Страница 15: ...e regulator diaphragm moves slightly higher allowing less gas flow to the gas control outlet This increases gas pressure under the automatic valve diaphragm and repositions the valve disk closer to the seat Thus flow of gas through the second automatic valve is reduced and outlet pressure falls to the desired level If outlet pressure begins to fall the pressure regulator diaphragmmovesslightlylowe...

Страница 16: ...N TRACING GAS FLOW SLOW OPENING GAS CONTROL HAS A GAS FLOW RESTRICTOR IN THIS PASSAGE M9126 1 1 PILOT GAS OUTLET Fig 15 Direct Ignition Intermittent Pilot Applications Position of gas control components during thermostat off cycle FIRST AUTOMATIC VALVE SOLENOID CONTROL KNOB GAS CONTROL INLET SECOND AUTOMATIC VALVE OPERATOR SECOND AUTOMATIC OPERATOR SOLENOID SECOND AUTOMATIC OPERATOR VALVE DISC SER...

Страница 17: ...m temperature while you are away COMPLETE SHUTDOWN Push in the gas control knob slightly and turn clockwise to OFF Do not force Appliance will completely shut off Follow the In structions to the Homeowner above to resume normal operation VR8345M SERVICE WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH Do not disassemble the gas control it contains no replaceable co...

Страница 18: ...68 0160 18 ...

Страница 19: ...19 68 0160 ...

Страница 20: ...ou Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY Printed on recycled paper containing at least 10 post consumer paper fibers ...

Отзывы: