Honeywell TRADELINE VR8345M Скачать руководство пользователя страница 12

68-0160

12

CAUTION

Stand clear while lighting main burner to prevent
injury caused from hidden gas leaks that could
cause flashback in the appliance vestibule.

3. Turn on the system by rotating the gas control knob

counterclockwise

to ON.

4. Light the main burner by following the appliance

manufacturer instructions or turning up the thermostat to call
for heat.

5. With the main burner in operation, paint all pipe joints

and gas control inlet and outlet with a rich soap and water
solution.

6. If another gas leak is detected, tighten joints and pipe

connections.

7. If gas leak cannot be stopped, turn the gas control knob

clockwise

to OFF.

8. Replace the leaking part.
9. Perform the gas leak test.

ADJUST THE PILOT BURNER FLAME (INTER-
MITTENT PILOT IGNITION ONLY)

The pilot flame should envelop 3/8 to 1/2 in. (10 to

13 mm) of the igniter-sensor tip. See Fig. 12. To adjust the
pilot flame:

1. Remove the pilot adjustment cover screw. Refer to

Fig. 4.

2. Turn  the  inner  adjustment  screw  clockwise            to

decrease or counterclockwise           to increase pilot flame.

3. To prevent gas leakage, always replace the cover

screw after adjustment.

Fig. 12—Proper flame adjustment.

PROPER FLAME 
ADJUSTMENT

IGNITER-
SENSOR 

M3080A

3/8 TO 1/2 INCH
(10 TO 13 mm)

CHECK AND ADJUST GAS INPUT TO MAIN
BURNER

CAUTION

1. Do not exceed the input rating stamped on the

appliance nameplate, or manufacturer recom-
mended burner orifice pressure for the size
orifice(s) used. Make certain the primary air
supply to the main burner is properly adjusted
for complete combustion (refer to the appliance
manufacturer instructions).

2. WHEN CHECKING GAS INPUT BY

CLOCKING THE GAS METER:
• Make sure that the only gas flow through the

meter is that of the appliance being checked.

• Make certain that other appliances are turned

off with pilot burners extinguished (or de-
duct that gas consumption from the meter
reading).

• Convert the flow rate to Btuh as described in

Gas Controls Handbook, form 70-2602, and
compare to the Btuh input rating on the
appliance nameplate.

3. WHEN CHECKING GAS INPUT WITH A

MANOMETER (PRESSURE GAUGE):
• To connect the manometer, be sure the gas

control knob is in the OFF position before
removing the outlet pressure tap plug.

• When removing the manometer, turn the gas

control knob back to OFF and replace the
outlet pressure tap plug.

• Shut off the gas supply at the appliance

service valve, or at the gas tank for LP gas,
before removing the outlet pressure tap plug
and before disconnecting the manometer and
replacing the outlet pressure tap plug.

• Perform the Gas Leak Test at the outlet

pressure tap plug.

Standard-Opening Pressure Regulator

1. The gas control outlet pressure should match the

manifold pressure listed on the appliance nameplate.

2. With the main burner operating, check the gas control

flow rate by using the meter clocking method or check the
gas pressure using a manometer connected to the gas control
outlet pressure tap. See Fig. 4.

3. If necessary, adjust the pressure regulator to match the

appliance rating. Refer to Table 5 for the factory-set nominal
outlet pressures and adjustment setting ranges.

a. Remove the pressure regulator adjustment cap screw.
b. Using a screwdriver, turn the inner adjustment screw

clockwise

to increase or counterclockwise

to decrease the main burner gas pressure.

c. Always replace the cap screw and tighten firmly to

safeguard proper operation.

VR8345M

STARTUP AND CHECKOUT

Содержание TRADELINE VR8345M

Страница 1: ...Works with virtually all residential equipment and all but the largest commercial equipment with a regulation capacity range of 30 000 to 415 000 Btuh natural gas 48 600 to 672 300 LP gas All adjustments and wiring connections accessible from top of control Straight through body pattern 1 8 in NPT inlet and outlet taps on top of gas control aid adjustment of gas pressure in problem installations 3...

Страница 2: ...conditions and some minor differences in performance can be expected if those conditions are changed MODEL VR8345M Universal Combination Gas Control AMBIENT TEMPERATURE RANGE 40 to 175 F 40 to 79 C BODY PATTERN Straight through REGULATOR TYPE Standard opening INLET X OUTLET SIZE 3 4 x 3 4 inch IGNITION ADAPTER Configures VR8345M to operate with direct spark or hot surface ignition ELECTRICAL RATIN...

Страница 3: ...ed service technician to re place the gas control Force or attempted repair can result in fire or explosion TABLE 3 VR8345 REPLACES THESE GAS CONTROLS Continued Replacement Gas Controls Universal Old Model No Manufacturer VR8200 VR8300 VR800 Replacement 36E36 304 DSI HSI WHITE RODGERS VR8205A2024 VR8305M3506 VR8450A4113 VR8345M4302a 36E36 304 IP WHITE RODGERS VR8204A2076 VR8304M3509 VR8440A3025 VR...

Страница 4: ...2024 VR8305M3506b VR8450A4113b VR8345M4302a b V8185A1001 HONEYWELL VR8205A2024 VR8305M3506 VR8450A4113 VR8345M4302a V8185A1019 HONEYWELL VR8205A2024 VR8305M3506 VR8450A4113 VR8345M4302a V8185A1035 HONEYWELL VR8205A2024 VR8305M3506 VR8450A4113 VR8345M4302a V8185B1009 HONEYWELL VR8205A2024 VR8305M3506 VR8450A4113 VR8345M4302a V8185B1017 HONEYWELL VR8205A2024 VR8305M3506 VR8450A4113 VR8345M4302a V824...

Страница 5: ...302e VR8440A2134 HONEYWELL VR8204A2076c VR8304M3509 VR8440A3025c VR8345M4302c VR8440A2142 HONEYWELL VR8204A2076 VR8304M3509 VR8440A3025 VR8345M4302 VR8440M1000 HONEYWELL VR8204A2076 VR8304M3509 VR8440A3025 VR8345M4302 VR8440M2008 HONEYWELL VR8204A2076 VR8304M3509 VR8440A3025 VR8345M4302 VR8440M2016 HONEYWELL VR8204A2076c VR8304M3509 VR8440A3025c VR8345M4302c VR8440M2024 HONEYWELL VR8204A2076 VR830...

Страница 6: ...with 1 8 in compression fitting part no 3934014 1 f Use with 3 4 in angle flange part no 393690 15 g Requires 1 2 in straight flange part no 393690 16 or an angle flange part no 393690 13 CAUTION Never apply a jumper across or short the valve coil terminals This can burn out the heat anticipator in the thermostat or damage the electronic intermit tent pilot IP module IMPORTANT These gas controls a...

Страница 7: ...tional Fuel Gas Code ANSI Z223 1 NFPA No 54 whichever applies Tubing installation must comply with approved standards and practices 1 Use new properly reamed pipe free from chips If tubing is used make sure the ends are square deburred and clean Make sure all tubing bends are smooth and without deformation 2 Run pipe or tubing to the gas control If tubing is used obtain a tube to pipe coupling to ...

Страница 8: ...ing to pilot burner manufacturer instructions Fig 6 Always use new compression fitting OUTLET PRESSURE TAP INLET OUTLET WIRING TERMINALS 2 INLET PRESSURE TAP PRESSURE REGULATOR ADJUSTMENT UNDER CAP SCREW CONVENIENCE TERMINALS 2 OPTIONAL PILOT OUTLET PILOT ADJUSTMENT UNDER CAP SCREW GAS CONTROL KNOB M8436 MUST USE WIRE ADAPTER NOT SHOWN ON HSI OR DSI SYSTEM MUST USE PILOT PLUG NOT SHOWN ON HSI OR D...

Страница 9: ...be in the valve pilot opening M8440 PV M V PV M V OFF ON PILOT GAS SEAL PLUG WIRE ADAPTER All wiring including insulated quick connect terminals mustcomplywithapplicableelectricalcodesandordinances 1 Check the power supply rating on the gas control and make sure it matches the available supply Install thermostat and other controls as required 2 When the gas control is installed on a hot surface or...

Страница 10: ...OR Q354 FLAME SENSOR LIMIT CONTROLLER THERMOSTAT OR CONTROLLER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED MAKE SURE L1 AND L2 ARE NOT REVERSED THIS WOULD PREVENT FLAME DETECTION ALTERNATE LIMIT CONTROLLER LOCATION SENSE TERMINAL AND Q354 FLAME SENSOR ON D MODELS ONLY BURNER GROUND M8563 QUICK CONNECTS AUTO IGNITION SYSTEMS ANSI Z21 20 STATUS LED 1 Flash Ignition Lock...

Страница 11: ...JURY OR DEATH Check for gas leaks with a rich soap and water solution anytime work is done on a gas control GAS LEAK TEST 1 Paint all pipe connections upstream of the gas control with a rich soap and water solution Bubbles indicate a gas leak 2 If a gas leak is detected tighten the pipe connection WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH 1 Donotforcethegasc...

Страница 12: ...CKING GAS INPUT BY CLOCKING THE GAS METER Make sure that the only gas flow through the meter is that of the appliance being checked Makecertainthatotherappliancesareturned off with pilot burners extinguished or de duct that gas consumption from the meter reading Convert the flow rate to Btuh as described in Gas Controls Handbook form 70 2602 and compare to the Btuh input rating on the appliance na...

Страница 13: ...programshouldincluderegularcheck out of the gas control see Startup and Checkout section To check out the control system see the appliance manufac turerliterature Maintenancefrequencymustbedetermined individually for each application Some considerations are Cycling frequency For appliances that may cycle 100 000 times annually check monthly Intermittent use For appliances that are used season ally...

Страница 14: ...lls for heat the DI module generates a spark at the main burner and the first automatic valve and second automatic valve operators are energized Fig 14 The first automatic valve opens and the second automatic valve operator valve disk is lifted off its seat This diverts gas flow from the second automatic valve diaphragm and causes a reduction of pressure on the underside of this diaphragm The redu...

Страница 15: ...e regulator diaphragm moves slightly higher allowing less gas flow to the gas control outlet This increases gas pressure under the automatic valve diaphragm and repositions the valve disk closer to the seat Thus flow of gas through the second automatic valve is reduced and outlet pressure falls to the desired level If outlet pressure begins to fall the pressure regulator diaphragmmovesslightlylowe...

Страница 16: ...N TRACING GAS FLOW SLOW OPENING GAS CONTROL HAS A GAS FLOW RESTRICTOR IN THIS PASSAGE M9126 1 1 PILOT GAS OUTLET Fig 15 Direct Ignition Intermittent Pilot Applications Position of gas control components during thermostat off cycle FIRST AUTOMATIC VALVE SOLENOID CONTROL KNOB GAS CONTROL INLET SECOND AUTOMATIC VALVE OPERATOR SECOND AUTOMATIC OPERATOR SOLENOID SECOND AUTOMATIC OPERATOR VALVE DISC SER...

Страница 17: ...m temperature while you are away COMPLETE SHUTDOWN Push in the gas control knob slightly and turn clockwise to OFF Do not force Appliance will completely shut off Follow the In structions to the Homeowner above to resume normal operation VR8345M SERVICE WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH Do not disassemble the gas control it contains no replaceable co...

Страница 18: ...68 0160 18 ...

Страница 19: ...19 68 0160 ...

Страница 20: ...ou Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY Printed on recycled paper containing at least 10 post consumer paper fibers ...

Отзывы: