background image

T8024D PROGRAMMABLE MULTISTAGE THERMOSTAT

69-1387-1

2

Fig. 1. Typical location of thermostat.

Fig. 2. Mounting wallplate to wall.

Wiring

IMPORTANT

Use an 18-gauge maximum wire for wiring the 
T8024 Thermostat.

All wiring must comply with local electrical codes and 

ordinances. Disconnect the power supply to prevent 
electrical shock or equipment damage.

NOTE: To ensure proper mounting of thermostat, 

restrict all wiring to the shaded area. See Fig. 3.

The shape of the terminals permits insertion of straight or 
wraparound wiring connections; either method is 

acceptable. See Fig. 4.

The T8024 Thermostat is powered through the system 
transformer and is adaptable to most 24 Vac multistage 

heating-cooling systems. Refer to Fig. 5 for typical wiring 
hookups.

Fig. 3. Restrict wiring to shaded area.

5 FEET

[1.5 METERS]

YES

NO

NO

NO

M11338

M12202A

WALL

WALL  
ANCHORS (2)

WALLPLATE

WHEN USING WALL ANCHORS, DRILL 3/16 INCH 
HOLES FOR DRYWALL, 7/32 INCH HOLES FOR
PLASTER OR WOOD.

MOUNTING 
SCREWS (2)

1

1

KEEP WIRING IN
SHADED AREA

MOUNTING 
SCREW HOLE

MOUNTING 
SCREW HOLE

WIRING ENTRANCE
HOLE

M20211

G

C

R

Y

W1

Y2

W2

B

O

Содержание Tradeline T8024D

Страница 1: ...duct is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power supply before installation Location Install the thermostat about 5 ft 1 5m above the f...

Страница 2: ...e shape of the terminals permits insertion of straight or wraparound wiring connections either method is acceptable See Fig 4 The T8024 Thermostat is powered through the system transformer and is adaptable to most 24 Vac multistage heating cooling systems Refer to Fig 5 for typical wiring hookups Fig 3 Restrict wiring to shaded area 5 FEET 1 5 METERS YES NO NO NO M11338 M12202A WALL WALL ANCHORS 2...

Страница 3: ...nutes after the heating equipment turns on on most systems When using an electric heat thermostat the fan starts and stops with the heating equipment Slide the FAN switch in the bottom left corner of the thermostat to select the desired fan setting SYSTEM Switch System switch settings control thermostat operation as follows Cool The thermostat controls the cooling system Off Both heating and cooli...

Страница 4: ... 1d only pressing the key can be used to turn heat or cool outputs on and off Change the SYSTEM switch setting to test heat or cool outputs No action takes place If the system switch is in the Off position Examples System setting at HEAT If heat is on pressing the key turns it off if heat is off pressing the key turns it on System setting at COOL If cool is on pressing the key turns it off if cool...

Страница 5: ...ey to save all changes and return to normal operation Table 1 Heating Cycle Rates for Stage Two Heating a High efficiency furnace bRefer to equipment manufacturer s instructions PROGRAMMING The thermostat is flexible and can be programmed for different schedules for weekdays and weekends Four time periods are available during weekdays and weekends WAKE LEAVE RETURN and SLEEP IMPORTANT Always press...

Страница 6: ...C Refer to manufacturer s recommendations Allow compressor to remain off for five minutes before restarting 1 Slide the SYSTEM switch to Cool and the FAN switch to Auto 2 Press the key to lower the temperature setting several degrees below the room temperature After approximately five minutes the cooling equipment should start The fan starts and stops with the cool ing equipment 3 Press the key to...

Отзывы: