TC809EA1035 Monitor Module
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Honeywell Building Solutions
Honeywell House, Arlington Business Park
Bracknell, Berkshire
RG12 1EB, UK
HW-460-019 1 I56-3992-004
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer
to the control panel installation manual for detailed system information.
If the modules will be installed in an existing operational system, inform
the operator and local authority that the system will be temporarily out
of service. Disconnect power to the control panel before installing the
modules.
NOTICE: This manual should be left with the owner/user of this
equipment.
GENERAL DESCRIPTION
The TC809EA1035 monitor module can be installed in a single gang
junction box directly behind the monitored unit. Its small size and light
weight allow it to be installed without rigid mounting (see Figure 1). The
TC809EA1035 is intended for use in intelligent, two-wire systems where
the individual address of each module is selected using rotary decade
switches. It provides a two-wire initiating circuit for normally open
contact fire alarm and security devices.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module should only be connected to a
compatible control panel.
FIGURE 1:
C01063-00
MOUNTING AND WIRING
NOTE: This module is intended to be wired and mounted without rigid
connections inside a standard electrical box. All wiring must conform to
applicable local codes and regulations.
1. Connect the red (+) and black ( – ) wires to the positive and negative
leads of the communication loop.
2. Connect the violet (+) and yellow ( – ) wires to a two-wire, normally
open monitoring line.
3. Install the specified EOL resistor value to terminate the monitoring
line.
The EOL resistor for standard use is 47K Ohms – the other
resistors are for special use only.
4. Set the address on the module per job drawings.
5. Install the module in the desired mounting location.
FIGURE 2. TYPICAL CIRCUIT CONFIGURATION:
(+)
(–)
TO
NEXT
DEVICE
BLA
CK
RED
(+)
(–)
(+)
(–)
VIOLET
YELLOW
FIRE DETECTION AND
ALARM SYSTEM LOOP
47k EOL
INCLUDED
(ELR-47k)
COMPATIBLE
CONTROL
PANEL
ALL WIRING
SHOWN IS
SUPERVISED AND
POWER LIMITED
0
7 8
6
5
4
3
2
1
9
10
11
12
13
14
15
0
1
2
3
4
5 6
7 8 9
C0614-05
SPECIFICATIONS
Communications Loop
Nominal Operating Voltage:
15-32 VDC
Average Operating Current:
400 µA, 1 comm. every 5 seconds,
(Standard 47K EOL)
Maximum Alarm Current
600 µA
Monitoring Line
EOL Resistance:
47K Ohms Standard
Maximum Wiring Resistance:
1.5K Ohms
Maximum Voltage to EOL:
11 Volts
Maximum Short Circuit Current:
217 µA
I56-3992-004
General
Temperature Range:
-10°C to 55°C
Humidity:
10% to 93% Non-condensing
Dimensions:
33mm H x 71mm W x 15mm D
Wire Length:
150mm minimum
COMMUNICATION LOOP
MONITORING LINE
ENGLISH
EOL
RESISTOR
INCLUDED
(47K OHMS
STANDARD
- ELR-47K)
0359
13
EN 54-18: 2005
Input Output Device
TC809EA1035
DOP-IOD005
System Sensor de México S.A. de C.V.
Ave. Valle del Cedro No. 1681, Parque Industrial Intermex
Ciudad Juárez, Chihuahua, CP 32574, Mexico