background image

TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS

15

62-2018—05

Channel

Channel selection

Default value = 

10

Set to: 

15

 or 

25

Range is: 10 to 26

Conditional parameter to wireless models (TB73xxX5x14W)

This parameter will only appear when a wireless network adapter is 

present. If the thermostat is installed as a stand-alone unit or is a 

BACnet model, this parameter will not be used or displayed

This parameter (Channel) is used to link specific thermostats to a 

specific WEBs controller with a wireless communication card. For 

every thermostat reporting to a gateway (maximum of 30 

thermostats per WEB-2xx controller and 50 thermostats per WEB-

6xx/-7xx controller) be sure you set the 

SAME

 channel value both at 

the wireless communication card and the thermostat(s).

Honeywell recommends using only the channels 15 (2425 MHz) 

or 25 (2575 MHz).

The default value of 10 is 

NOT

 a valid channel. Although the valid 

range of available channels is from 11 to 26 use only channel 15 or 

25 to avoid interference with other wireless devices.

Get From

Default value = 

255

Range is: 0-254

Conditional parameter to wireless models (TB73xxX5x14W)

This parameter is only available for wireless thermostats. This 

parameter lets you to copy the configuration parameter settings from 

a like Honeywell TB7200 thermostat. To use this command, the 

thermostat you want to copy parameters from must be on the 

wireless network with a network address (

Com addr

) and must be 

the same model number as the thermostat you want to copy to.

On the thermostat you want to copy parameters to, enter the network 

address (

Com addr

) of the thermostat you want to copy parameters 

from. This process can be completed locally at the thermostat or 

using the WEBStation-AX.

If the parameters copy successfully, the 

Get From

 address returns to 

255

. If the parameters do not copy successfully, 

254

 is displayed. If 

the copy was not successful, verify the following:

The thermostat to be copied is the same model as the one being 

copied to.

The thermostat to be copied is on the network.

The correct network address (

Com addr

) value for the thermostat 

to be copied was entered. 

Leaving the 

Get From

 parameter value at 

255

 means that 

configuration parameters will be set manually.

BI1

Binary input no.1 configuration

Default value

 

None

(None):

 No function will be associated with the input 

(Rem NSB):

 remote NSB timer clock input. The scheduling will now 

be set as per the binary input. It provides low cost setback operation 

via a dry contact

Contact opened = Occupied

Contact closed = Unoccupied

(Motion NO) or (Motion NC):

 Advanced PIR occupancy functions 

using a Normally Open (NO) or Normally Closed (NC) remote PIR 

motion sensor. Occupancy mode is now set as per applied PIR 

function and configuration.

Application information is available in the PIR Application Guide for 

TB7300 Series Thermostats (Form No. 63-4526). This document 

provides installers and system designers with detailed examples on 

applications, parameter configuration, sequence of operations, 

troubleshooting and diagnostic help required for proper use of 

occupancy sensor models.

(Window) 

EMS: Forces the system to disable any current heating or 

cooling action by the thermostat. The mode stays the same and the 

current setpoints are the same Occupied setpoints. Only the outputs 

are disabled. There is a Door/Window alarm displayed on the 

thermostat to indicate to the local tenant that the door/window needs 

to be closed for cooling or heating to resume.

NOTE: These settings will disable the local override function 

on the thermostat.

Table 11. Configuration parameters

Configuration 

parameters

Default value

Significance and adjustments

Содержание TB7300A5014B

Страница 1: ...FEATURES Available in BACnet MS TP and Zigbee wireless protocols Backlit LCD display with dedicated function menu keys for simple operation Internal humidity sensing for increased occupant comfort through dehumidification on some models Fully integrated advanced occupancy functionality with a PIR cover provides energy savings opportunity on select models all other models are PIR ready and can have...

Страница 2: ...og 1 Aux RH Ready TB7355F5514B Hotel Fan Coil Unit 2 analog 1 Aux RH Yes Wireless Models TB7300A5014W Commercial Fan Coil Unit 2 digital 1 Aux Ready TB7300A5514W Commercial Fan Coil Unit 2 digital 1 Aux Yes TB7300C5014W Commercial Fan Coil Unit 2 floating 1 Aux Ready TB7300C5514W Commercial Fan Coil Unit 2 floating 1 Aux Yes TB7300F5014W Commercial Fan Coil Unit 2 analog 1 Aux Ready TB7300F5514W C...

Страница 3: ...ould not be installed near an air discharge grill Should not be mounted in direct sun radiation Nothing must restrain vertical air circulation to the thermostat Wall surface must be flat and clean IMPORTANT If replacing an old thermostat label the wires before removal of the old thermostat CAUTION Electronic controls are static sensitive devices Discharge yourself properly before manipulation and ...

Страница 4: ... holes on each side of the base and mount base on wall Fig 2 9 Gently swing back the circuit board back to the base and push on it until the tabs lock it in place 10 Strip each wire 1 4 inch 11 Wire the terminals for the desired application See Table 1 for terminal descriptions and wiring diagrams 12 Gently push back excess cable into hole 13 Install wiring terminals in correct location Fig 3 14 R...

Страница 5: ...eed Fan H 2 Medium Fan Speed Fan M Fan M 2 Medium Fan Speed Fan M 3 Low Fan Speed Fan L Fan L 3 Low Fan Speed Fan L 4 24 V Hot 24 V Hot 24 V Hot 4 24 V Hot 24 V Hot 5 24 V Com 24 V Com 24 V Com 5 24 V Com 24 V Com 6 Aux BO 5 BO 5 Aux BO 5 Aux 6 Aux BO 5 BO 5 Aux 7 Aux BO 5 BO 5 Aux BO 5 Aux 7 Aux BO 5 BO 5 Aux 8 BO 3 Open Heat BO 3 BO 3 Blank 9 BO 4 Close Heat BO 4 9 AO 2 Heat AO 2 10 BO 1 Open Co...

Страница 6: ...1014 Scom RS TB WALL 1014 TB WALL 1014 AND TB WALLOVR 1014 CAN BE MIXED AND MATCHED TB WALL 1014 AND TB WALLOVR 1014 ARE TO BE WIRED IN PARALLELL ENSURE THE DIP SWITCH SETTINGS ARE CORRECT IN EACH REMOTE SENSOR 1 1 Scom RS AUX C DI TB WALLOVR 1014 DIP SWITCHES S1 ON S2 OFF Scom RS AUX C DI TB WALLOVR 1014 TB7200 TB7300 THERMOSTAT TB7200 TB7300 THERMOSTAT TB7200 TB7300 THERMOSTAT DIP SWITCHES S1 ON...

Страница 7: ...947 HIGH MED LOW HIGH HIGH LOW DRY CONTACT TO END DEVICE 24 V MAXIMUM 24 VAC POWER TO RELAY 4 24 V HOT 5 24 V COM 6 7 4 24 V HOT 5 24 V COM 6 7 R R M16949 24 V HOT 24 V COM N C HEATING COOLING VALVE BO 2 24 VAC COM M16960 24 V HOT 24 V COM N O HEATING VALVE BO 3 24 VAC COM BO 2 N C COOLING VALVE 24 VAC COM M16961 24 V HOT 24 V COM HEATING COOLING VALVE BO1 BO2 IF N O IF N C 24 VAC COM OR M16924 24...

Страница 8: ...oating valve cooling and or heating Mandatory Pipe no 2 pipes CntrltTyp Floating Fan Menu 0 L M H FL time as per actuator If cooling only set SeqOpera 0 Cooling only If heating only set SeqOpera 1 Heating only If heat cool auto changeover with a local water temperature sensor set SeqOpera 0 Cooling only UI3 COS 2 Pipe applications 4 Pipe applications 24 V HOT 24 V COM HEATING COOLING VALVE AO 1 CO...

Страница 9: ... CntrltTyp Floating Fan Menu 0 L M H FL time as per actuator SeqOpera 4 Cool Heat 4 pipe system cooling and heating TB7300F5x14 x and TB7305F5x14 x analog actuators Modulating analog valve cooling and heating Mandatory Pipe no 4 pipes Fan Menu 0 L M H RA DA as per actuator SeqOpera 4 Cool Heat Schematic Wiring Settings ROOM TEMPERATURE CONTROL THERMOSTAT 3 SPEED FAN M16950 24 VAC FAN RELAYS HIGH M...

Страница 10: ... with RH sensor built in Display function can be enabled with RH display parameter Displayed range is 10 to 90 RH OUTDOOR AIR TEMPERATURE Display is only enabled when outdoor air temperature network variable is received OCCUPANCY STATUS Occupied Stand By Unoccupied and Override status are displayed on the scrolling display ALARMS If alarms are detected they will automatically be displayed at the e...

Страница 11: ... the programmable binary input BI2 Filter Indicates that the filters are dirty as per one of the programmable binary input BI2 Window Indicates that the outside window or door is opened and that the thermostat has cancelled any cooling or heating action BI1 System Is used to toggle between the different system modes available as per sequence and menu selected Pressing repetitively the button will ...

Страница 12: ...on taken by the thermostat or the one currently in use If the other setpoint is the one desired then the MODE button is used to toggle between the current displayed one and the other Cool XX X F or C Heat XX X F or C No access to setpoint Cool XX X F or C or Heat XX X F or C Toggle to Heat or Cool with MODE button Cooling mode Heating mode Off mode Auto Mode Setpoint presented to user is the setpo...

Страница 13: ...emperature offset from setpoint Low speed operates on demand and will shut down when no demand is present Sequence selected Mode Menu 0 Cooling only Off Cool 1 Heating only Off Heat 2 Cooling With Reheat Off Auto Heat Cool 3 Heating With Reheat Off Heat 4 Cooling Heating 4 pipes Off Auto Heat Cool 5 Cooling Heating 4 pipes with Reheat Off Auto Heat Cool Sequence selected Mode Menu 0 Cooling only O...

Страница 14: ...ill scroll all available parameters one by one Down Adjust parameter value down Up Adjust parameter value up Table 11 Configuration parameters Configuration parameters Default value Significance and adjustments PswrdSet Configuration parameters menu access password Default value 0 Range is 0 to 1000 This parameter sets a protective access password to prevent unauthorized access to the configuratio...

Страница 15: ...on AX If the parameters copy successfully the Get From address returns to 255 If the parameters do not copy successfully 254 is displayed If the copy was not successful verify the following The thermostat to be copied is the same model as the one being copied to The thermostat to be copied is on the network The correct network address Com addr value for the thermostat to be copied was entered Leav...

Страница 16: ...e AC unit control card which provides an alarm in case of malfunction Contact opened No alarm Contact closed Alarm displayed UI3 Universal input no 3 configuration Default value None None No function will be associated with the input COC NH Change over dry contact Normally Heat Used when both heating and cooling are controlled from the same thermostat output Contact closes when cold air water is p...

Страница 17: ...Table 12 Keypad Lockout Levels Level Occupiedtemperature setpoints System mode setting Fan mode setting Unoccupied Override 0 Yes access Yes access Yes access Yes access 1 Yes access Yes access Yes access No access 2 Yes access No access No access Yes access 3 Yes access No access No access No access 4 No access No access No access Yes access 5 No access No access No access No access Default value...

Страница 18: ...r 0 0 hours Setting this parameter to its default value of 0 0 hours disables the unoccupied timer This prevents the thermostat to drift from stand by mode to unoccupied mode when PIR functions are used Range is 0 0 to 24 0 hours in 0 5 hr increments St By HT Stand by heating setpoint Default value 69 F The value of this parameter should reside between the occupied and unoccupied heating setpoints...

Страница 19: ...ny change of occupied or unoccupied setpoints through the keypad by the user are permanent and saved to and EEPROM Spt Func Local setpoint settings Default value Dual Spt Set the local setpoint interface for the user Dual Spt Dual Occupied Setpoints Adjustment Attch Spt Single Occupied Setpoint Adjustment TOccTime Temporary occupancy time Default value 2 hours Temporary occupancy time with occupie...

Страница 20: ...cupied periods AS AD Auto Speed Auto Demand during occupied periods FL time Floating actuator timing Default value 1 5 minutes For floating models TB73xxC5x14 x only Maximum stroke time of floating valve actuator Range is 0 5 to 9 0 minutes in 0 5 minutes increment cph On Off devices cycles per hour Default value 4 cph For on off models and sequences TB73xxC5x14 x only Will set the maximum number ...

Страница 21: ...d bulk polymer type sensor Humidity sensor precision Reading range from 10 90 R H non condensing 10 to 20 precision is 10 20 to 80 precision is 5 80 to 90 precision is 10 Humidity sensor stability Less than 1 0 yearly typical drift Dehumidification setpoint range 30 to 95 R H Occ Stand By and Unocc cooling setpoint range 54 to 100 F 12 0 to 37 5 C Occ Stand By and Unocc heating setpoint range 40 F...

Страница 22: ...e and 2 this device must accept any interference received including interference that may cause undesired operation Agency Approvals BACnet models BTL IMPORTANT All TB7300 series controls are for use as operating controls only and are not safety devices These instru ments have undergone rigorous tests and verifications prior to shipment to ensure proper and reliable opera tion in the field Wheneve...

Страница 23: ...TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS 23 62 2018 05 ...

Страница 24: ...STATS Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2011 Honeywell International Inc 62 2018 05 M S Rev 09 11 Printed in United States ...

Отзывы: