TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
62-2018—05
10
THERMOSTAT USER INTERFACE
The thermostat features a two-line, eight-character display. There is a low level backlight level that is always active and
can only be seen at night. To turn on the back light to high level, press any key on the front panel. The back lit display
will return to low level when the thermostat is left unattended for 45 seconds
When left unattended, the thermostat has an auto scrolling display that shows the actual status of the system. Use the
MenuScro
in the configuration menu to lockout the scrolling display and to only present the room temperature and
conditional outdoor temperature to the user. With this option enabled, no local status is given on the system mode or
occupancy.
Each item is scrolled one by one with the back lighting in low level mode. Pressing any key will cause the back light to
come on to high level. When left unattended for 10 seconds after changes are made, the display will resume automatic
status display scrolling.
Table 3. Sequence and possible display options for the auto-scroll display
* Network value only
**If humidity display is enabled
***If humidity display is not enabled
% RH DISPLAY IS CONDITIONAL TO:
• Models with RH sensor built in.
• Display function can be enabled with RH display parameter. Displayed range is 10 to 90% RH.
OUTDOOR AIR TEMPERATURE
• Display is only enabled when outdoor air temperature network variable is received.
OCCUPANCY STATUS
• Occupied, Stand-By, Unoccupied and Override status are displayed on the scrolling display.
ALARMS
• If alarms are detected, they will automatically be displayed at the end of the status display scroll.
• During an alarm message display, the backlit screen will light up at the same time as the message and shut off
during the rest of the status display.
• Two alarms maximum can appear at any given time. The priority for the alarms is as follows:
2 pipe system cooling or heating with reheat: TB7300C5x14(x) and TB7305C5x14(x) floating actuator
Modulating floating valve
cooling and/or heating
Mandatory
• Pipe no
= 2 pipes
• CntrltTyp
= Floating
• Fan Menu
= 0 (L-M-H)
• FL time
=
as per actuator
• SeqOpera
= 2 Cool/Reheat
• UI3
= COS
Room Temp and
Humidity
>
System mode
>
Schedule status
>
Outdoor Temp*
>
Alarms
x.x °C or °F
xx % RH
**
Sys mode
auto
Occupied
Outdoor
x.x °C or°F
Service
RoomTemp
x.x °C or °F
***
Sys mode
cool
Stand-By
Filter
Sys mode
heat
Unoccup
Window
Sys mode
off
Override
Schematic
Wiring
Settings
ROOM TEMPERATURE
CONTROL THERMOSTAT
3 SPEED FAN
ELECTRIC
REHEAT
M16952
24 VAC
FAN RELAYS
HIGH
MED
LOW
FAN-H
FAN-M
BO 5
BO 5
FAN-L
UI 3 COS
24 V~ COM
24 V ~ HOT
BO 2 CLOSE
BO 1 OPEN
OPTIONAL SUPPLY WATER
TEMPERATURE SENSOR
M16959