TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS

62-2018—05

14

INSTALLER CONFIGURATION PARAMETER MENU

This section describes the parameters available for TB7300 Series thermostat configuration. The TB7300 Series can 

be programmed at the thermostat or through WEBStation-AX, with the following exception: Wireless models must have 

the 

Com Addr

PAN ID

, and 

Channel 

set at the thermostat before adding to the wireless network or doing any 

programming in WEBStation-AX.

To program the thermostat through WEBStation-AX, refer to the BACnet Integration Reference Guide for BACnet 

models (Form No. 63-4524) or the Wireless Installation and Integration Reference Guide for TB7200, TB7300, TB7600 

Thermostats (Form No. 63-4522) for wireless models.

Local configuration:

1.

To enter configuration, press and hold the middle button (°C/°F or Override) for 8 seconds

2.

If a password lockout is active, “Password” is prompted. Enter password value using the “up” and “down” arrows 

and press the middle button again to gain access to all configuration properties of the thermostat. A wrong pass-

word entered will prevent local access to the configuration menu.

3.

Press the same middle button repetitively to scroll between all the available parameters

4.

Use the up and down key to change the parameter to the desired value.

5.

To acknowledge and save the new value, press the middle button again.

6.

The next listed parameter is now displayed.

Table 10. Configuration interface

Fan

Re-starts the configuration parameter list at the beginning.

°C/°F 

Override

Enters the configuration mode. Press and hold for 8 seconds.

Pressing repetitively will scroll all available parameters one by one.

Down

Adjust parameter value down.

Up

Adjust parameter value up.

Table 11. Configuration parameters

Configuration 

parameters

Default value

Significance and adjustments

PswrdSet

Configuration parameters menu 

access password

Default value = 

0

Range is: 0 to 1000

This parameter sets a protective access password to prevent 

unauthorized access to the configuration menu parameters. A default 

value of “0” will not prompt a password or lock the access to the 

configuration menu.

Range is:

 

0 to 1000

Com Addr 

Thermostat networking address

Default value = 

254

Range is: 0 to 254

 If the thermostat is installed as a stand-alone unit, this parameter 

will not be used or displayed

For BACnet models valid range to use is from 0 to 127. Default value 

of 254 disables BACnet communication for the thermostat.

For wireless models valid range is 0 to 254 with a maximum of 30 

thermostats per WEB-2xx controller and 50 thermostats per WEB-

6xx/-7xx controller.

PAN ID

Personal Area Network 

Identification

Default value = 

0

Range is: 0 to 500

Conditional parameter to wireless models (TB73xxX5x14W)

This parameter will only appear on wireless thermostats. If the 

thermostat is BACnet, this parameter will not be used or displayed

This parameter (Personal Area Network Identification) is used to link 

specific thermostats to a single specific WEBs controller with a 

wireless communication card (TB-VWG-APP-1014). For every 

thermostat reporting to a WEBs controller and wireless 

communication card (maximum of 30 thermostats per WEB-2xx 

controller and 50 thermostats per WEB-6xx/-7xx controller) be sure 

you set the 

SAME

 

PAN ID

 value both at the wireless communication 

card and the thermostat(s). 

The default value of 0 is 

NOT

 a valid PAN ID. The valid range of 

available PAN ID is from 1 to 500

Содержание TB7300A5014B

Страница 1: ...FEATURES Available in BACnet MS TP and Zigbee wireless protocols Backlit LCD display with dedicated function menu keys for simple operation Internal humidity sensing for increased occupant comfort through dehumidification on some models Fully integrated advanced occupancy functionality with a PIR cover provides energy savings opportunity on select models all other models are PIR ready and can have...

Страница 2: ...og 1 Aux RH Ready TB7355F5514B Hotel Fan Coil Unit 2 analog 1 Aux RH Yes Wireless Models TB7300A5014W Commercial Fan Coil Unit 2 digital 1 Aux Ready TB7300A5514W Commercial Fan Coil Unit 2 digital 1 Aux Yes TB7300C5014W Commercial Fan Coil Unit 2 floating 1 Aux Ready TB7300C5514W Commercial Fan Coil Unit 2 floating 1 Aux Yes TB7300F5014W Commercial Fan Coil Unit 2 analog 1 Aux Ready TB7300F5514W C...

Страница 3: ...ould not be installed near an air discharge grill Should not be mounted in direct sun radiation Nothing must restrain vertical air circulation to the thermostat Wall surface must be flat and clean IMPORTANT If replacing an old thermostat label the wires before removal of the old thermostat CAUTION Electronic controls are static sensitive devices Discharge yourself properly before manipulation and ...

Страница 4: ... holes on each side of the base and mount base on wall Fig 2 9 Gently swing back the circuit board back to the base and push on it until the tabs lock it in place 10 Strip each wire 1 4 inch 11 Wire the terminals for the desired application See Table 1 for terminal descriptions and wiring diagrams 12 Gently push back excess cable into hole 13 Install wiring terminals in correct location Fig 3 14 R...

Страница 5: ...eed Fan H 2 Medium Fan Speed Fan M Fan M 2 Medium Fan Speed Fan M 3 Low Fan Speed Fan L Fan L 3 Low Fan Speed Fan L 4 24 V Hot 24 V Hot 24 V Hot 4 24 V Hot 24 V Hot 5 24 V Com 24 V Com 24 V Com 5 24 V Com 24 V Com 6 Aux BO 5 BO 5 Aux BO 5 Aux 6 Aux BO 5 BO 5 Aux 7 Aux BO 5 BO 5 Aux BO 5 Aux 7 Aux BO 5 BO 5 Aux 8 BO 3 Open Heat BO 3 BO 3 Blank 9 BO 4 Close Heat BO 4 9 AO 2 Heat AO 2 10 BO 1 Open Co...

Страница 6: ...1014 Scom RS TB WALL 1014 TB WALL 1014 AND TB WALLOVR 1014 CAN BE MIXED AND MATCHED TB WALL 1014 AND TB WALLOVR 1014 ARE TO BE WIRED IN PARALLELL ENSURE THE DIP SWITCH SETTINGS ARE CORRECT IN EACH REMOTE SENSOR 1 1 Scom RS AUX C DI TB WALLOVR 1014 DIP SWITCHES S1 ON S2 OFF Scom RS AUX C DI TB WALLOVR 1014 TB7200 TB7300 THERMOSTAT TB7200 TB7300 THERMOSTAT TB7200 TB7300 THERMOSTAT DIP SWITCHES S1 ON...

Страница 7: ...947 HIGH MED LOW HIGH HIGH LOW DRY CONTACT TO END DEVICE 24 V MAXIMUM 24 VAC POWER TO RELAY 4 24 V HOT 5 24 V COM 6 7 4 24 V HOT 5 24 V COM 6 7 R R M16949 24 V HOT 24 V COM N C HEATING COOLING VALVE BO 2 24 VAC COM M16960 24 V HOT 24 V COM N O HEATING VALVE BO 3 24 VAC COM BO 2 N C COOLING VALVE 24 VAC COM M16961 24 V HOT 24 V COM HEATING COOLING VALVE BO1 BO2 IF N O IF N C 24 VAC COM OR M16924 24...

Страница 8: ...oating valve cooling and or heating Mandatory Pipe no 2 pipes CntrltTyp Floating Fan Menu 0 L M H FL time as per actuator If cooling only set SeqOpera 0 Cooling only If heating only set SeqOpera 1 Heating only If heat cool auto changeover with a local water temperature sensor set SeqOpera 0 Cooling only UI3 COS 2 Pipe applications 4 Pipe applications 24 V HOT 24 V COM HEATING COOLING VALVE AO 1 CO...

Страница 9: ... CntrltTyp Floating Fan Menu 0 L M H FL time as per actuator SeqOpera 4 Cool Heat 4 pipe system cooling and heating TB7300F5x14 x and TB7305F5x14 x analog actuators Modulating analog valve cooling and heating Mandatory Pipe no 4 pipes Fan Menu 0 L M H RA DA as per actuator SeqOpera 4 Cool Heat Schematic Wiring Settings ROOM TEMPERATURE CONTROL THERMOSTAT 3 SPEED FAN M16950 24 VAC FAN RELAYS HIGH M...

Страница 10: ... with RH sensor built in Display function can be enabled with RH display parameter Displayed range is 10 to 90 RH OUTDOOR AIR TEMPERATURE Display is only enabled when outdoor air temperature network variable is received OCCUPANCY STATUS Occupied Stand By Unoccupied and Override status are displayed on the scrolling display ALARMS If alarms are detected they will automatically be displayed at the e...

Страница 11: ... the programmable binary input BI2 Filter Indicates that the filters are dirty as per one of the programmable binary input BI2 Window Indicates that the outside window or door is opened and that the thermostat has cancelled any cooling or heating action BI1 System Is used to toggle between the different system modes available as per sequence and menu selected Pressing repetitively the button will ...

Страница 12: ...on taken by the thermostat or the one currently in use If the other setpoint is the one desired then the MODE button is used to toggle between the current displayed one and the other Cool XX X F or C Heat XX X F or C No access to setpoint Cool XX X F or C or Heat XX X F or C Toggle to Heat or Cool with MODE button Cooling mode Heating mode Off mode Auto Mode Setpoint presented to user is the setpo...

Страница 13: ...emperature offset from setpoint Low speed operates on demand and will shut down when no demand is present Sequence selected Mode Menu 0 Cooling only Off Cool 1 Heating only Off Heat 2 Cooling With Reheat Off Auto Heat Cool 3 Heating With Reheat Off Heat 4 Cooling Heating 4 pipes Off Auto Heat Cool 5 Cooling Heating 4 pipes with Reheat Off Auto Heat Cool Sequence selected Mode Menu 0 Cooling only O...

Страница 14: ...ill scroll all available parameters one by one Down Adjust parameter value down Up Adjust parameter value up Table 11 Configuration parameters Configuration parameters Default value Significance and adjustments PswrdSet Configuration parameters menu access password Default value 0 Range is 0 to 1000 This parameter sets a protective access password to prevent unauthorized access to the configuratio...

Страница 15: ...on AX If the parameters copy successfully the Get From address returns to 255 If the parameters do not copy successfully 254 is displayed If the copy was not successful verify the following The thermostat to be copied is the same model as the one being copied to The thermostat to be copied is on the network The correct network address Com addr value for the thermostat to be copied was entered Leav...

Страница 16: ...e AC unit control card which provides an alarm in case of malfunction Contact opened No alarm Contact closed Alarm displayed UI3 Universal input no 3 configuration Default value None None No function will be associated with the input COC NH Change over dry contact Normally Heat Used when both heating and cooling are controlled from the same thermostat output Contact closes when cold air water is p...

Страница 17: ...Table 12 Keypad Lockout Levels Level Occupiedtemperature setpoints System mode setting Fan mode setting Unoccupied Override 0 Yes access Yes access Yes access Yes access 1 Yes access Yes access Yes access No access 2 Yes access No access No access Yes access 3 Yes access No access No access No access 4 No access No access No access Yes access 5 No access No access No access No access Default value...

Страница 18: ...r 0 0 hours Setting this parameter to its default value of 0 0 hours disables the unoccupied timer This prevents the thermostat to drift from stand by mode to unoccupied mode when PIR functions are used Range is 0 0 to 24 0 hours in 0 5 hr increments St By HT Stand by heating setpoint Default value 69 F The value of this parameter should reside between the occupied and unoccupied heating setpoints...

Страница 19: ...ny change of occupied or unoccupied setpoints through the keypad by the user are permanent and saved to and EEPROM Spt Func Local setpoint settings Default value Dual Spt Set the local setpoint interface for the user Dual Spt Dual Occupied Setpoints Adjustment Attch Spt Single Occupied Setpoint Adjustment TOccTime Temporary occupancy time Default value 2 hours Temporary occupancy time with occupie...

Страница 20: ...cupied periods AS AD Auto Speed Auto Demand during occupied periods FL time Floating actuator timing Default value 1 5 minutes For floating models TB73xxC5x14 x only Maximum stroke time of floating valve actuator Range is 0 5 to 9 0 minutes in 0 5 minutes increment cph On Off devices cycles per hour Default value 4 cph For on off models and sequences TB73xxC5x14 x only Will set the maximum number ...

Страница 21: ...d bulk polymer type sensor Humidity sensor precision Reading range from 10 90 R H non condensing 10 to 20 precision is 10 20 to 80 precision is 5 80 to 90 precision is 10 Humidity sensor stability Less than 1 0 yearly typical drift Dehumidification setpoint range 30 to 95 R H Occ Stand By and Unocc cooling setpoint range 54 to 100 F 12 0 to 37 5 C Occ Stand By and Unocc heating setpoint range 40 F...

Страница 22: ...e and 2 this device must accept any interference received including interference that may cause undesired operation Agency Approvals BACnet models BTL IMPORTANT All TB7300 series controls are for use as operating controls only and are not safety devices These instru ments have undergone rigorous tests and verifications prior to shipment to ensure proper and reliable opera tion in the field Wheneve...

Страница 23: ...TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS 23 62 2018 05 ...

Страница 24: ...STATS Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2011 Honeywell International Inc 62 2018 05 M S Rev 09 11 Printed in United States ...

Отзывы: