TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
62-2018—05
14
INSTALLER CONFIGURATION PARAMETER MENU
This section describes the parameters available for TB7300 Series thermostat configuration. The TB7300 Series can
be programmed at the thermostat or through WEBStation-AX, with the following exception: Wireless models must have
the
Com Addr
,
PAN ID
, and
Channel
set at the thermostat before adding to the wireless network or doing any
programming in WEBStation-AX.
To program the thermostat through WEBStation-AX, refer to the BACnet Integration Reference Guide for BACnet
models (Form No. 63-4524) or the Wireless Installation and Integration Reference Guide for TB7200, TB7300, TB7600
Thermostats (Form No. 63-4522) for wireless models.
Local configuration:
1.
To enter configuration, press and hold the middle button (°C/°F or Override) for 8 seconds
2.
If a password lockout is active, “Password” is prompted. Enter password value using the “up” and “down” arrows
and press the middle button again to gain access to all configuration properties of the thermostat. A wrong pass-
word entered will prevent local access to the configuration menu.
3.
Press the same middle button repetitively to scroll between all the available parameters
4.
Use the up and down key to change the parameter to the desired value.
5.
To acknowledge and save the new value, press the middle button again.
6.
The next listed parameter is now displayed.
Table 10. Configuration interface
Fan
Re-starts the configuration parameter list at the beginning.
°C/°F
Override
Enters the configuration mode. Press and hold for 8 seconds.
Pressing repetitively will scroll all available parameters one by one.
Down
Adjust parameter value down.
Up
Adjust parameter value up.
Table 11. Configuration parameters
Configuration
parameters
Default value
Significance and adjustments
PswrdSet
Configuration parameters menu
access password
Default value =
0
Range is: 0 to 1000
This parameter sets a protective access password to prevent
unauthorized access to the configuration menu parameters. A default
value of “0” will not prompt a password or lock the access to the
configuration menu.
Range is:
0 to 1000
Com Addr
Thermostat networking address
Default value =
254
Range is: 0 to 254
If the thermostat is installed as a stand-alone unit, this parameter
will not be used or displayed
For BACnet models valid range to use is from 0 to 127. Default value
of 254 disables BACnet communication for the thermostat.
For wireless models valid range is 0 to 254 with a maximum of 30
thermostats per WEB-2xx controller and 50 thermostats per WEB-
6xx/-7xx controller.
PAN ID
Personal Area Network
Identification
Default value =
0
Range is: 0 to 500
Conditional parameter to wireless models (TB73xxX5x14W)
This parameter will only appear on wireless thermostats. If the
thermostat is BACnet, this parameter will not be used or displayed
This parameter (Personal Area Network Identification) is used to link
specific thermostats to a single specific WEBs controller with a
wireless communication card (TB-VWG-APP-1014). For every
thermostat reporting to a WEBs controller and wireless
communication card (maximum of 30 thermostats per WEB-2xx
controller and 50 thermostats per WEB-6xx/-7xx controller) be sure
you set the
SAME
PAN ID
value both at the wireless communication
card and the thermostat(s).
The default value of 0 is
NOT
a valid PAN ID. The valid range of
available PAN ID is from 1 to 500