BACNET® FIXED FUNCTION THERMOSTAT

7

31-00093—01

Pairing a Sensor to a Wireless 
BACnet FF (TB3026B-W Only)

BACnet FFs and sensors ship unpaired, verified by two 
dashes in the Sensor Status field on the BACnet FF’s 
Wireless Sensor Setup screen. To pair them, issue a pairing 
command from the BACnet FF and then activate the 
sensor. 

Accessed from Field Service Mode (See “Field Service 
Mode” on page 7), the 
BACnet FF’s Wireless Sensor Setup 
Mode includes diagnostic screens for configuration and 
checkout of associated sensors. With :UC displayed in 
Field Service Mode, press the blank key (blank area) just to 
the left of the blank center key, and then press the down 
arrow key next to the :UC parameter.

Door/window sensors may be paired to any available 
sensor number in the range 1-8. When cycling through 
sensor numbers on the Wireless Sensor Setup screen, 
unpaired sensor numbers show a status of --. 

PIR sensors may be paired to any available sensor number 
in the range 1-3.

Fig. 9. Wireless Sensor Setup screen.

TO PAIR A SENSOR TO A BACNET FF

1.

Make sure the battery is installed and activated in 
the sensor. 

2.

If the sensor is a door/window switch, align the mag-
net so that the sensor is in the closed position. If the 
sensor is a PIR sensor, cover the PIR. 

IMPORTANT

 Verify that the sliding door/window contact is 
closed and cover all other PIRs to prevent interfer-
ence during the pairing process.

3.

On the BACnet FF select the sensor to pair and then 
press Reset. The RESET key disappears and WAIT is 
displayed indicating that the BACnet FF is waiting to 
pair the sensor with the next device that receives a 
radio signal.

4.

Activate the sensor to be paired. 

NOTE:

Pairing times out after 10 seconds of no 
pairing activity.

5.

Verify that the BACnet FF and sensor successfully 
paired.
Paired = sensor status is displayed, replacing --.
Timed out = RESET is displayed and sensor status
is --.

Fig. 10. Door sensor number 1 paired and in closed 

status.

TO ERASE SENSOR-TO-BACNET FF PAIRINGS

1.

While viewing any sensor status screen while pairing 
is not taking place, press the blank key to the left of 
CANCEL.

2.

Press the blank key to the right of DONE. 
The sensor status field displays --, indicating 
unpaired.

FIELD SERVICE MODE

Fixed Field Service Codes

Field service mode enables technicians to query and 
command key operating variables in the BACnet FF while 
at the BACnet FF touchscreen. A technician presses a 
particular key sequence at the BACnet FF to enter field 
service mode. In field service mode a technician uses the 
left arrows to scroll through data codes and the right 
arrows to change the value associated with a code.

The lower left of the LCD shows the two-digit data code 
and the main area displays the data value. A pre-defined 
list of data codes is available within the description of 
each application. See BACnet Fixed Function Thermostat 
System Engineering Guide (31-00098) for the complete 
list of setup codes.

Users can be denied access to field service mode by 
setting BV-68 to ON. A PIN code can also be required to 
enter field service mode by setting AV-132 to the desired 
PIN number.

Field service mode ends automatically if there is no key 
activity for five minutes.

Setting Field Service Codes

To set field service codes

1.

From the home screen, press SYSTEM. Five blank 
touch keys will appear at the bottom of the screen.

2.

Press and hold the center bottom key for approxi-
mately five seconds (see Fig. 11).

Содержание TB3026B

Страница 1: ...ls are TB3026B and TB3026B W which includes a wireless sensor option INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check ratings given in instructions and on the product to ensure the product is suitable for the application 3 Installer must be a trained experienced service technician 4 ...

Страница 2: ...n a 4 in x 2 in 101 6 mm x 50 8 mm wiring box 1 Position and level the wallplate for appearance only 2 Use a pencil to mark the mounting holes see Fig 3 3 Drill two pilot holes in the wall on the marks For dry wall drill 3 16 in holes For firmer material such as plaster drill 7 32 in holes Gently tap anchors pro vided into the pilot holes until flush with the wall 4 Pull the wires through the wiri...

Страница 3: ... Analog Output 16 GND Ground 17 BO2 Relay Output 18 BO3 Relay Output 19 BO4 Relay Output 20 BO5 Relay Output Table 2 MS TP LAN facts Transmission speed 9 6 19 2 38 4 76 8Kbps configured at global controller Layout Bus Cabling BACnet specifies the following Shielded twisted pair cabling with characteristic impedance between 100 and 130W Distributed capacitance between conductors must be less than 3...

Страница 4: ...es and becomes more square When the resistance value increases the amplitude of the wave form increases and becomes less square Typically precision resistors in the range 80 130 Ohms 1 yield acceptable results Ideally the value of the terminating resistors should match the rated characteristic impedance of the installed cable For example if the installed MS TP cable has a listed characteristic imp...

Страница 5: ...one to exit installer setup For example if the MAC address is 15 and the device instance to 1876 use these settings ISU code 800 15 ISU code 801 0 ISU code 802 00 ISU code 803 18 ISU code 804 76 Installer Setup ISU Codes Installer setup mode provides access to functions specific to installation of a BACnet FF Some BACnet FF configuration parameters can be altered from the ISU screens The ISU param...

Страница 6: ... Hum pad change reminder AV 125 0 reminder not used 1 90 days 2 180 days 3 365 days 520 UV lamp change reminder AV 126 0 reminder not used 1 365 days 540 Program periods AV 129 2 Wake Sleep 4 Wake Leave Return Sleep 640 Clock format BV 83 12 12 hour BV 83 0 24 24 hour BV 83 1 670 Keypad lock AV 128 0 no lock 1 access temperature settings only 2 fully locked 700 Sensed room temperature offset AV 13...

Страница 7: ...a radio signal 4 Activate the sensor to be paired NOTE Pairing times out after 10 seconds of no pairing activity 5 Verify that the BACnet FF and sensor successfully paired Paired sensor status is displayed replacing Timed out RESET is displayed and sensor status is Fig 10 Door sensor number 1 paired and in closed status TO ERASE SENSOR TO BACNET FF PAIRINGS 1 While viewing any sensor status screen...

Страница 8: ...ersal inputs with 12 bit accuracy providing con trolled voltage current and resistive modes Internal Sensors 1 internal temperature sensor 0 120 deg F 17 8 48 9 deg C 1 internal humidity 5 95 RH non condens ing Relay Outputs 6 relay outputs normally open contacts with a maximum switch rating of 24VAC 0 5A 12VA BO 0 BO 2 and BO 5 are powered from the controller transformer BO 1 BO 3 and BO 4 are po...

Отзывы: