BACNET® FIXED FUNCTION THERMOSTAT

31-00093—01

6

Table 3. ISU Parameters.

ISU Parameter 

Code

Description

Allowed Values

120

Year, first 2 digits

19-21

130

Year, second 2 digits

00-99 (00-54 if ISU 200=21)

140

Month

1-12

150

Day

1-31

160

Schedule format BV-133 0 – not programmable (BV-133=0) 4 – 7 day programmable (BV-133=1)

280

Backlight control BV-79 0 – on for 20 seconds after keypress 

1 – low always on, bright after keypress

320

Swap English/Metric 
BV-69

1 – show opposite units to specified in DDC header

330

Daylight saving
 AV-127

0 – off; no automatic adjustments
1 – pre 2007 scheme
2 – 2007 and later scheme

500

Filter change reminder
AV-124

0 – reminder not used
1 – 10 days
2 – 30 days
3 – 60 days
4 – 90 days
5 – 120 days
6 – 365 days

510

Hum pad change 
reminder
AV-125

0 – reminder not used
1 – 90 days
2 – 180 days
3 – 365 days

520

UV lamp change 
reminder
AV-126

0 – reminder not used
1 – 365 days

540

Program periods
AV-129

2 – Wake/Sleep
4 – Wake/Leave/Return/Sleep

640

Clock format
BV-83

12 – 12 hour (BV-83=0)
24 – 24 hour (BV-83=1)

670

Keypad lock
AV-128

0 – no lock
1 – access temperature settings only
2 – fully locked

700

Sensed room 
temperature offset (AV-
138)

-4 to +4 degrees F

701

Sensed room humidity 
offset (AV-139)

-5% TO +5%
Humidity cannot be adjusted above 100% or below 0%.

702

Sensed outside air 
temperature offset (AV-
140)

-4 to +4 degrees F

703

Sensed outside humidity 
offset (AV-141)

-5% TO +5%
Humidity cannot be adjusted above 100% or below 0%.

800

MS/TP MAC

0-127

801

BACnet Device Instance 
- first digit

0-4

802

BACnet Device Instance 
second and third digits

00-99

803

BACnet Device Instance 
forth and fifth digits

00-99

804

BACnet Device Instance 
sixth and seventh digits

00-99

Содержание TB3026B

Страница 1: ...ls are TB3026B and TB3026B W which includes a wireless sensor option INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check ratings given in instructions and on the product to ensure the product is suitable for the application 3 Installer must be a trained experienced service technician 4 ...

Страница 2: ...n a 4 in x 2 in 101 6 mm x 50 8 mm wiring box 1 Position and level the wallplate for appearance only 2 Use a pencil to mark the mounting holes see Fig 3 3 Drill two pilot holes in the wall on the marks For dry wall drill 3 16 in holes For firmer material such as plaster drill 7 32 in holes Gently tap anchors pro vided into the pilot holes until flush with the wall 4 Pull the wires through the wiri...

Страница 3: ... Analog Output 16 GND Ground 17 BO2 Relay Output 18 BO3 Relay Output 19 BO4 Relay Output 20 BO5 Relay Output Table 2 MS TP LAN facts Transmission speed 9 6 19 2 38 4 76 8Kbps configured at global controller Layout Bus Cabling BACnet specifies the following Shielded twisted pair cabling with characteristic impedance between 100 and 130W Distributed capacitance between conductors must be less than 3...

Страница 4: ...es and becomes more square When the resistance value increases the amplitude of the wave form increases and becomes less square Typically precision resistors in the range 80 130 Ohms 1 yield acceptable results Ideally the value of the terminating resistors should match the rated characteristic impedance of the installed cable For example if the installed MS TP cable has a listed characteristic imp...

Страница 5: ...one to exit installer setup For example if the MAC address is 15 and the device instance to 1876 use these settings ISU code 800 15 ISU code 801 0 ISU code 802 00 ISU code 803 18 ISU code 804 76 Installer Setup ISU Codes Installer setup mode provides access to functions specific to installation of a BACnet FF Some BACnet FF configuration parameters can be altered from the ISU screens The ISU param...

Страница 6: ... Hum pad change reminder AV 125 0 reminder not used 1 90 days 2 180 days 3 365 days 520 UV lamp change reminder AV 126 0 reminder not used 1 365 days 540 Program periods AV 129 2 Wake Sleep 4 Wake Leave Return Sleep 640 Clock format BV 83 12 12 hour BV 83 0 24 24 hour BV 83 1 670 Keypad lock AV 128 0 no lock 1 access temperature settings only 2 fully locked 700 Sensed room temperature offset AV 13...

Страница 7: ...a radio signal 4 Activate the sensor to be paired NOTE Pairing times out after 10 seconds of no pairing activity 5 Verify that the BACnet FF and sensor successfully paired Paired sensor status is displayed replacing Timed out RESET is displayed and sensor status is Fig 10 Door sensor number 1 paired and in closed status TO ERASE SENSOR TO BACNET FF PAIRINGS 1 While viewing any sensor status screen...

Страница 8: ...ersal inputs with 12 bit accuracy providing con trolled voltage current and resistive modes Internal Sensors 1 internal temperature sensor 0 120 deg F 17 8 48 9 deg C 1 internal humidity 5 95 RH non condens ing Relay Outputs 6 relay outputs normally open contacts with a maximum switch rating of 24VAC 0 5A 12VA BO 0 BO 2 and BO 5 are powered from the controller transformer BO 1 BO 3 and BO 4 are po...

Отзывы: