Grounding the MS/TP LAN Shield

Proper shield grounding of the MS/TP cabling can help 
minimize the risk of communications problems and 
damage to equipment because of transient voltage spikes 
(for example, lightning strikes).

Follow these guidelines for grounding MS/TP cable 
shields:
• Each MS/TP segment should have a single point of 

shield ground, preferably as close to the middle of the 
cabling run as possible.

• Do not ground the MS/TP shield using a BACnet FF 

terminal.

• Never ground both ends of a shield; differences in 

potential between the grounds may induce current on 
the shield, causing interference.

• At termination connecting points, tie the shield through 

with a wire nut.

• At ungrounded, exposed shield points (the end of a 

segment), tape back the shield to the wire jacket or, for 
optimum transient shunting, use 100V gas discharge 
tubes or 120V MOVs between shield and ground.

Terminating Resistors

Matched terminating resistors wired across MS/TP+ and 
MS/TP– are required at the last device on each end of the 
MS/TP segment for signal integrity (Fig. 5).

Optimum segment performance typically requires 
“tuning,” a process by which the value of the terminating 
resistors is selected based on the wave form of signals on 
the segment. View wave forms using an industrial scope 
meter. The goal is to have as square a wave form as 
possible with an amplitude greater than 200 mV. Resistors 
affect the wave form as follows:
• When the resistance value decreases, the amplitude of 

the wave form decreases and becomes more square.

• When the resistance value increases, the amplitude of 

the wave form increases and becomes less square.

Typically, precision resistors in the range 80-130 Ohms 
(+1%) yield acceptable results. Ideally, the value of the 
terminating resistors should match the rated 
characteristic impedance of the installed cable. For 
example, if the installed MS/TP cable has a listed 
characteristic impedance of 100 Ohm, install 100 Ohm 
matched precision resistors.

CAUTION

Do not mismatch terminating resistors.

Ensure that both resistors on a segment have the 
same value.

NOTE:

Typically, White is Data - and Black is Data +.

Fig. 5. Terminating resistor detail.

Mounting Thermostat to Wallplate

1.

Align the terminal screw blocks with the pins on the 
back of the thermostat.

2.

Push the thermostat straight onto the wallplate.

Fig. 6. Thermostat mounting.

NOTE:

To remove the thermostat from the wall, first pull 
out at the bottom of the thermostat; then remove 
the top.

CONFIGURATION

Once the BACnet FF is mounted and wired, configure it 
from the BACnet FF touchscreen.

Adjusting the Date and Time

When the controller is first powered up, the date and time 
might need to be set. These are set at the factory, but the 
on-board power supply may have run down. If this 
happens, adjust the date and time. 

TO ADJUST THE TIME

1.

Touch Clock at the bottom of the screen.

2.

Use the arrows to adjust the year, month, and day.

3.

Press DONE.

4.

Adjust the time and press DONE.

Setting the MAC Address and 
Device Instance

The factory default MAC address is 0. Valid MAC 
addresses are 0-127. The default device instance is 
0009999. Valid device instances are 0-4194302.

NOTE:

The device instance can also be set using a 
BACnet Supervisor

WALL

M19919

REMOVE DURING INST

ALLA

TION

Содержание TB3026B

Страница 1: ...ls are TB3026B and TB3026B W which includes a wireless sensor option INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check ratings given in instructions and on the product to ensure the product is suitable for the application 3 Installer must be a trained experienced service technician 4 ...

Страница 2: ...n a 4 in x 2 in 101 6 mm x 50 8 mm wiring box 1 Position and level the wallplate for appearance only 2 Use a pencil to mark the mounting holes see Fig 3 3 Drill two pilot holes in the wall on the marks For dry wall drill 3 16 in holes For firmer material such as plaster drill 7 32 in holes Gently tap anchors pro vided into the pilot holes until flush with the wall 4 Pull the wires through the wiri...

Страница 3: ... Analog Output 16 GND Ground 17 BO2 Relay Output 18 BO3 Relay Output 19 BO4 Relay Output 20 BO5 Relay Output Table 2 MS TP LAN facts Transmission speed 9 6 19 2 38 4 76 8Kbps configured at global controller Layout Bus Cabling BACnet specifies the following Shielded twisted pair cabling with characteristic impedance between 100 and 130W Distributed capacitance between conductors must be less than 3...

Страница 4: ...es and becomes more square When the resistance value increases the amplitude of the wave form increases and becomes less square Typically precision resistors in the range 80 130 Ohms 1 yield acceptable results Ideally the value of the terminating resistors should match the rated characteristic impedance of the installed cable For example if the installed MS TP cable has a listed characteristic imp...

Страница 5: ...one to exit installer setup For example if the MAC address is 15 and the device instance to 1876 use these settings ISU code 800 15 ISU code 801 0 ISU code 802 00 ISU code 803 18 ISU code 804 76 Installer Setup ISU Codes Installer setup mode provides access to functions specific to installation of a BACnet FF Some BACnet FF configuration parameters can be altered from the ISU screens The ISU param...

Страница 6: ... Hum pad change reminder AV 125 0 reminder not used 1 90 days 2 180 days 3 365 days 520 UV lamp change reminder AV 126 0 reminder not used 1 365 days 540 Program periods AV 129 2 Wake Sleep 4 Wake Leave Return Sleep 640 Clock format BV 83 12 12 hour BV 83 0 24 24 hour BV 83 1 670 Keypad lock AV 128 0 no lock 1 access temperature settings only 2 fully locked 700 Sensed room temperature offset AV 13...

Страница 7: ...a radio signal 4 Activate the sensor to be paired NOTE Pairing times out after 10 seconds of no pairing activity 5 Verify that the BACnet FF and sensor successfully paired Paired sensor status is displayed replacing Timed out RESET is displayed and sensor status is Fig 10 Door sensor number 1 paired and in closed status TO ERASE SENSOR TO BACNET FF PAIRINGS 1 While viewing any sensor status screen...

Страница 8: ...ersal inputs with 12 bit accuracy providing con trolled voltage current and resistive modes Internal Sensors 1 internal temperature sensor 0 120 deg F 17 8 48 9 deg C 1 internal humidity 5 95 RH non condens ing Relay Outputs 6 relay outputs normally open contacts with a maximum switch rating of 24VAC 0 5A 12VA BO 0 BO 2 and BO 5 are powered from the controller transformer BO 1 BO 3 and BO 4 are po...

Отзывы: