Honeywell TB3026B Скачать руководство пользователя страница 5

BACNET® FIXED FUNCTION THERMOSTAT

5

31-00093—01

TO SET THE MAC ADDRESS AND DEVICE INSTANCE AT 
THE DISPLAY

1.

From the home screen, press SYSTEM. Five blank 
touch keys will appear at the bottom of the screen.

2.

Press and hold the two blank keys on either side of 
the center key for approximately five seconds (see 
Fig. 7).

Fig. 7. Entering ISU mode.

The installer setup (ISU) screen appears. An ISU code is 
displayed in the lower left. It is a four-digit code beginning 
with zero. The current setting is displayed in the lower 
right.

 

Fig. 8. ISU screen.

3.

Use the down arrow next to the installer setup code 
to advance to ISU code 800.

4.

Use the up and down arrows next to the current set-
ting to set ISU code 800 (MAC address) to a value 
between 0 and 127.

NOTE:

Set ISU code 801 (first digit of device 
instance) to a value between 0 and 4.

5.

The device instance is set by entering values in four 
separate ISU codes. See example on page 5.

6.

Set ISU code 802 (second and third digits of device 
instance) to a value between 00 and 99.

7.

Set ISU code 803 (fourth and fifth digits of device 
instance) to a value between 00 and 99.

8.

Set ISU code 804 (sixth and seventh digits of device 
instance) to a value between 0 and 99.

9.

Press Done to exit installer setup.

For example, if the MAC address is 15 and the device 
instance to 1876, use these settings:

ISU code 800=15
ISU code 801=0
ISU code 802=00
ISU code 803=18
ISU code 804=76

Installer Setup (ISU) Codes

Installer setup mode provides access to functions specific 
to installation of a BACnet FF. Some BACnet FF 
configuration parameters can be altered from the ISU 
screens. The ISU parameters can also be accessed via 
BACnet.

A PIN can be required to access ISU mode by setting AV-
133 to a non-zero, four-digit number.

For a complete application configuration guide, refer to 
the BACnet Fixed Function Thermostat System 
Engineering Guide (31-00098) and WEBs-AX 
Configuration Guide (31-00097) 

TO ACCESS THE ISU SCREENS

1.

From the home screen, press SYSTEM. Five blank 
touch keys will appear at the bottom of the screen.

2.

Press and hold the two blank keys on either side of 
the center key for approximately five seconds (see 
Fig. 7).

3.

If a PIN code is required, use the top arrows to select 
the first two digits of the code and the bottom arrows 
to select the third and fourth digits of the code, and 
then press DONE.

The ISU screen appears.

4.

Use the arrows to select parameters and values. See 
Table 3 for details.

5.

Press DONE.

NOTE:

After five minutes of inactivity, the ISU 
screen reverts to the main screen.

DONE

CANC

MO

TU

WE

TH

FR

SA

SU

SYSTE

M

EM

HEAT

OFF

Following
Schedule

Inside

Set To

M19923

Содержание TB3026B

Страница 1: ...ls are TB3026B and TB3026B W which includes a wireless sensor option INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check ratings given in instructions and on the product to ensure the product is suitable for the application 3 Installer must be a trained experienced service technician 4 ...

Страница 2: ...n a 4 in x 2 in 101 6 mm x 50 8 mm wiring box 1 Position and level the wallplate for appearance only 2 Use a pencil to mark the mounting holes see Fig 3 3 Drill two pilot holes in the wall on the marks For dry wall drill 3 16 in holes For firmer material such as plaster drill 7 32 in holes Gently tap anchors pro vided into the pilot holes until flush with the wall 4 Pull the wires through the wiri...

Страница 3: ... Analog Output 16 GND Ground 17 BO2 Relay Output 18 BO3 Relay Output 19 BO4 Relay Output 20 BO5 Relay Output Table 2 MS TP LAN facts Transmission speed 9 6 19 2 38 4 76 8Kbps configured at global controller Layout Bus Cabling BACnet specifies the following Shielded twisted pair cabling with characteristic impedance between 100 and 130W Distributed capacitance between conductors must be less than 3...

Страница 4: ...es and becomes more square When the resistance value increases the amplitude of the wave form increases and becomes less square Typically precision resistors in the range 80 130 Ohms 1 yield acceptable results Ideally the value of the terminating resistors should match the rated characteristic impedance of the installed cable For example if the installed MS TP cable has a listed characteristic imp...

Страница 5: ...one to exit installer setup For example if the MAC address is 15 and the device instance to 1876 use these settings ISU code 800 15 ISU code 801 0 ISU code 802 00 ISU code 803 18 ISU code 804 76 Installer Setup ISU Codes Installer setup mode provides access to functions specific to installation of a BACnet FF Some BACnet FF configuration parameters can be altered from the ISU screens The ISU param...

Страница 6: ... Hum pad change reminder AV 125 0 reminder not used 1 90 days 2 180 days 3 365 days 520 UV lamp change reminder AV 126 0 reminder not used 1 365 days 540 Program periods AV 129 2 Wake Sleep 4 Wake Leave Return Sleep 640 Clock format BV 83 12 12 hour BV 83 0 24 24 hour BV 83 1 670 Keypad lock AV 128 0 no lock 1 access temperature settings only 2 fully locked 700 Sensed room temperature offset AV 13...

Страница 7: ...a radio signal 4 Activate the sensor to be paired NOTE Pairing times out after 10 seconds of no pairing activity 5 Verify that the BACnet FF and sensor successfully paired Paired sensor status is displayed replacing Timed out RESET is displayed and sensor status is Fig 10 Door sensor number 1 paired and in closed status TO ERASE SENSOR TO BACNET FF PAIRINGS 1 While viewing any sensor status screen...

Страница 8: ...ersal inputs with 12 bit accuracy providing con trolled voltage current and resistive modes Internal Sensors 1 internal temperature sensor 0 120 deg F 17 8 48 9 deg C 1 internal humidity 5 95 RH non condens ing Relay Outputs 6 relay outputs normally open contacts with a maximum switch rating of 24VAC 0 5A 12VA BO 0 BO 2 and BO 5 are powered from the controller transformer BO 1 BO 3 and BO 4 are po...

Отзывы: