Fig. 11. Entering Field Service mode.

3.

The field service screen appears.

NOTE:

If a PIN code is required, use the top arrows 
to select the first two digits of the code and 
the bottom arrows to select the third and 
fourth digits of the code, and then press 
DONE.

4.

Press the left up or down arrows until the desired 
code appears.

5.

Press the right up or down arrows to adjust the value 
associated with the code.

6.

Press the left up or down arrows to accept the 
change and scroll to a different code.

7.

Press DONE to exit field service mode.

TECHNICAL DATA

Power

24VAC power from a UL Listed Class-2 24VAC transformer 

(not provided). The BACnet FF uses a half-wave rectifier 
to convert the AC power supply to onboard power. This 
enables multiple devices with half-wave power supplies 
to be powered from a single, grounded transformer.

Min. Load = 17VA (all BOs OFF).
Max. Load = 89VA (all BOs ON).
If BO power jumper is not removed, then all BOs are pow-

ered from the controller’s transformer.

Minimum load includes controller and analog outputs at 

full load (20mA into 500 Ohms).

All BOs are N.O. (Normally Open) contacts with a maxi-

mum switch rating of 24VAC @ 0.5A (12VA).

Maximum load assumes all 6 relay output loads are pow-

ered from the controller transformer and connected 
loads are the maximum allowed (24VAC @ 0.5A). Actual 
power requirements depend on connected loads.

Wireless Receiver (TB3026B-W only)

433.92 Mhz; range is 50 feet.

Inputs

3 universal inputs with 12-bit accuracy, providing con-

trolled voltage, current and resistive modes.

Internal Sensors

1 internal temperature sensor, 0–120 deg. F (-17.8–48.9 

deg. C); 1 internal humidity, 5–95% RH, non-condens-
ing.

Relay Outputs

6 relay outputs; normally open contacts with a maximum 

switch rating of 24VAC @ 0.5A (12VA). BO-0, BO-2 and 
BO-5 are powered from the controller transformer. BO-
1, BO-3 and BO-4 are powered from control trans-
former through removable jumper, allowing these BOs 
to be powered from a separate power source.

Universal Analog Outputs

2 outputs with 12-bit resolution. Each auto-detects for 0–

10VDC or 4–20mA. 4–20mA outputs are sourced by the 
VLD. Connected loads must return to the VLD ground. 
The BACnet FF automatically switches from 0–10V 
mode to 4–20mA current mode when it detects a load 
value of less than 500 Ohms.

Processor & Memory

Powerful 32-bit processor with extensive flash memory 

and RAM resources. Flash memory provides nonvola-
tile program and data storage, and allows for encrypted 
updates to the program for future product enhance-
ments.

Environmental

Residential, commercial and light-industrial environ-

ments. 0–120 deg. F (-17–49 deg. C). 0–95% RH, non-
condensing.

Communications

BACnet MS/TP LAN up to 76.8Kbps.

Ratings

Listed Underwriters Laboratory for Open Energy Manage-

ment Equipment (PAZX) under the UL Standard for 
Safety 916; listing includes both U.S. and Canadian 
certification.

EMC Directive (European CE Mark) EN 60950 (VLD-362-

FF model only). 

FCC Part 15, Class B.

More Information

To learn more about these products, visit

http://customer.honeywell.com

• BACnet Fixed Function Thermostat Product Data 

(Form No. 31-00096)

• BACnet Fixed Function Thermostat WEBs-AX 

Configuration Wizard Guide (Form No. 31-00097)

• BACnet Fixed Function Thermostat System 

Engineering Guide (Form No. 31-00098)

DONE

CANCEL

TUE

PM

SYSTEM

OFF

COOL

CHANGE FILTER UV LAMP 

Following
Schedule

Inside

M22766

Содержание TB3026B

Страница 1: ...ls are TB3026B and TB3026B W which includes a wireless sensor option INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check ratings given in instructions and on the product to ensure the product is suitable for the application 3 Installer must be a trained experienced service technician 4 ...

Страница 2: ...n a 4 in x 2 in 101 6 mm x 50 8 mm wiring box 1 Position and level the wallplate for appearance only 2 Use a pencil to mark the mounting holes see Fig 3 3 Drill two pilot holes in the wall on the marks For dry wall drill 3 16 in holes For firmer material such as plaster drill 7 32 in holes Gently tap anchors pro vided into the pilot holes until flush with the wall 4 Pull the wires through the wiri...

Страница 3: ... Analog Output 16 GND Ground 17 BO2 Relay Output 18 BO3 Relay Output 19 BO4 Relay Output 20 BO5 Relay Output Table 2 MS TP LAN facts Transmission speed 9 6 19 2 38 4 76 8Kbps configured at global controller Layout Bus Cabling BACnet specifies the following Shielded twisted pair cabling with characteristic impedance between 100 and 130W Distributed capacitance between conductors must be less than 3...

Страница 4: ...es and becomes more square When the resistance value increases the amplitude of the wave form increases and becomes less square Typically precision resistors in the range 80 130 Ohms 1 yield acceptable results Ideally the value of the terminating resistors should match the rated characteristic impedance of the installed cable For example if the installed MS TP cable has a listed characteristic imp...

Страница 5: ...one to exit installer setup For example if the MAC address is 15 and the device instance to 1876 use these settings ISU code 800 15 ISU code 801 0 ISU code 802 00 ISU code 803 18 ISU code 804 76 Installer Setup ISU Codes Installer setup mode provides access to functions specific to installation of a BACnet FF Some BACnet FF configuration parameters can be altered from the ISU screens The ISU param...

Страница 6: ... Hum pad change reminder AV 125 0 reminder not used 1 90 days 2 180 days 3 365 days 520 UV lamp change reminder AV 126 0 reminder not used 1 365 days 540 Program periods AV 129 2 Wake Sleep 4 Wake Leave Return Sleep 640 Clock format BV 83 12 12 hour BV 83 0 24 24 hour BV 83 1 670 Keypad lock AV 128 0 no lock 1 access temperature settings only 2 fully locked 700 Sensed room temperature offset AV 13...

Страница 7: ...a radio signal 4 Activate the sensor to be paired NOTE Pairing times out after 10 seconds of no pairing activity 5 Verify that the BACnet FF and sensor successfully paired Paired sensor status is displayed replacing Timed out RESET is displayed and sensor status is Fig 10 Door sensor number 1 paired and in closed status TO ERASE SENSOR TO BACNET FF PAIRINGS 1 While viewing any sensor status screen...

Страница 8: ...ersal inputs with 12 bit accuracy providing con trolled voltage current and resistive modes Internal Sensors 1 internal temperature sensor 0 120 deg F 17 8 48 9 deg C 1 internal humidity 5 95 RH non condens ing Relay Outputs 6 relay outputs normally open contacts with a maximum switch rating of 24VAC 0 5A 12VA BO 0 BO 2 and BO 5 are powered from the controller transformer BO 1 BO 3 and BO 4 are po...

Отзывы: